The GP2501-TC41-24V,GP2501-SC41-24V and the GP2601-TC41-24V are UL/
c-UL recognized components. (UL file No. E182139)
This Unit conforms as a component to the following standards:
UL508
Industrial Control Equipment
UL1604
Electrical Equipment for Use in Class I and II Division 2 and Class III Hazardous
(Classified) Locations
CAN/CSA-C22.2, No.1010-1 (c-UL Approval)
Safety Requirement for Electrical Equipment for Measurement, Control and
Laboratory Use
CSA-C22.2, No.213-1987 (c-UL Approval)
Non-incendive Electrical Equipment for Use in Class I, Division 2 Hazardous
Locations
GP2501-TC41-24V (UL Registration Model : 2880045-01)
GP2501-SC41-24V (UL Registration Model : 2980078-02)
GP2601-TC41-24V (UL Registration Model : 2880045-02)
<Cautions>
•
The GP must be used as a built-in component of an end-use product.
•
The GP units must be used indoors only.
•
The GP should be installed in the front face of a metal panel.
•
If the GP is installed so as to cool itself naturally, be sure to install it in a verti-
cal panel. Also, be sure that the GP is mounted at least 100mm away from
adjacent structures and other equipment, otherwise, the heat generated by the
GP's internal components may become higher than that allowed by UL stan-
dard requirements.
UL1604 Conditions of Acceptability and Handling Cautions:
1. Power, input and output (I/O) wiring must all be in accordance with Class I,
Division 2 wiring methods, Article 501-4 (b) of the National Electrical Code,
NFPA 70, or as specified in Section 18-152 of the Canadian Electrical Code
for units installed within Canada, and in accordance with that location's au-
thority.
2. Suitable for use in Class I, Division2, GroupsA, B, C and D hazardous loca-
tion.
3.
WARNING:
Explosion hazard - substitution of components may impair
suitability for Class I, Division 2.
4.
WARNING:
Explosion hazard - when in hazardous locations, turn off power
before replacing or wiring modules.
5.
WARNING:
Explosion hazard - do not disconnect equipment unless power
has been switched off or the area is known to be nonhazardous.
6.
WARNING
: Explosion hazard - do not connect/ disconnect equipment unless
area is known to be nonhazardous. Port is for system set up and diagnostics.
UL/c-UL Approval