E2-1
GP2000 Series VM Unit User Manual
Chapter 2 : SPECIFICATIONS
2.1
General Specifications
2.1.1
Electrical
2.1.2
Environmental
Rated Voltage
DC5V (Supplied from the GP Unit)
Allowable Voltage Range
DC4.75V to DC5.25V
Current Consumption
approx. 1.1 A
Insulation Endurance
AC1500V, 20 mA for up to 1 minute
(between GP unit charging and FG terminals)
Insulation Resistance
10 M
Ω
or more at DC500V
(between GP unit charging and FG terminals)
Ambient Operating
Temperature
Storage Temperature
Ambient Humidity
Storage Humidity
Dust
Atmosphere
When vibration is NOT continuous:
10 Hz to 57 Hz: 0.075 mm,
57 Hz to 150 Hz: 9.8 m/s
2
When vibration is continuous:
10 Hz to 57 Hz: 0.035 mm,
57 Hz to 150 Hz: 4.9 m/s
2
Noise Voltage:
Pulse Duration:
Rise Time:
1500 Vp-p (100 VAC power supply
1000 Vp-p (24 VDC power supply)
1
µ
s
1 ns
X, Y, Z directions for 10 times (80 min.)
IEC61131-2 compatible
Noise Immunity
(via noise simulator)
(via noise simulator)
Vibration Resistance
0.1 mg/m
3
or less (Non-conductive levels)
Free of corrosive gasses
0°C to +50°C
*1
-20°C to +60°C
10% RH to 90% RH
(non-condensing, wet bulb temperature: 39°C or less)
*1
10% RH to 90% RH
(non-condensing, wet bulb temperature: 39°C or less)
*1 Must be within the GP unit's ambient temperature/humidity range.
Содержание GP2000-VM41
Страница 1: ...GP2000 Series VM Unit User Manual...
Страница 19: ...E2 8 GP2000 Series VM Unit User Manual Memo...
Страница 31: ...E5 4 GP2000 Series VM Unit User Manual Memo...