Installation procedure
Step
Procedure Details
1
Cut an opening in the panel to match the standard mount or flat mount panel
cut dimensions, and then weld four M4 x 10L stud bolts perpendicular to the
rear surface of the panel in order to fix the GP unit in place.
Note:
z
Before you start this work, carefully read "3. Panel Cut Dimensions" (see
page 223).
z
Prepare four stud bolts and four nuts within your quality assurance range.
z
The stud bolt height is 10 mm (0.39 in.).
z
We recommend that you use M4 nuts (ISO4032, JIS B 1181).
PP
LQ
Installation diagram (profile)
PP
LQ