Specifications of Serial Interface COM2
Introduction
NOTE:
For instructions on how to connect to other devices, always refer to the “GP-
Pro EX Device/PLC Connection Manual”.
The COM2 ports of GP-4501T and GP-4501TW are not isolated. The SG (signal
ground) and FG (frame ground) terminals are connected inside the GP unit.
Serial Interface COM2
GP-4501T / GP-4501TW: D-Sub 9 pin plug connector via an RS-422/485 cable.
Interfit bracket is #4-40 (UNC).
Recommendations:
z
Cable Connector: XM2D-0901 manufactured by OMRON Corporation.
z
Cable Cover: XM2S-0913 manufactured by OMRON Corporation.
z
Jack Screw (#4-40 UNC): XM2Z-0073 manufactured by OMRON Corporation.
DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
z
Verify that a short-circuit loop is not created when you set up the system.
z
Connect the #5 SG terminal to remote equipment when the host (PLC) unit is
not isolated. Connect the #5 SG terminal to a known reliable ground connection
to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.
Pin Connection
Pin
No.
RS-422/RS-485
Signal Name
Direction
Meaning
1
RDA
Input
Receive Data A (+)
2
RDB
Input
Receive Data B (-)
3
SDA
Output
Send Data A (+)
4
ERA
Output
Data Terminal Ready A (+)
5
SG
-
Signal Ground
6
CSB
Input
Send Possible B (-)
7
SDB
Output
Send Data B (-)
8
CSA
Input
Send Possible A (+)
9
ERB
Output
Data Terminal Ready B (-)
Shell
FG
–
Frame Ground (Common
with SG)
CAUTION
LOSS OF COMMUNICATION
z
All connections to the communication ports must not put excessive stress on the
ports.
z
Securely attach communication cables to the panel wall or cabinet.
z
Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.
9
6
5
1
(GP unit side)
Содержание GP-4200 Series
Страница 1: ...3 6HULHV DUGZDUH 0DQXDO...
Страница 10: ...10...
Страница 42: ...Parts Functions 42...
Страница 58: ...Specifications 58 Dimensions External Dimensions 1 Front 2 Right Side 3 Top PP LQ...
Страница 110: ...Specifications 110 External Dimensions GP 4501TW 1 Front 2 Right Side 3 Top PP LQ...
Страница 134: ...Specifications 134...
Страница 161: ...GP4000 Series Hardware Manual 161 1 USB clamp 2 USB cable 2 1 1...
Страница 162: ...Installation and Wiring 162...