-15-
Analog Connection (DR
*
-B1
*
1BD)
Analog Connection (DR
*
-B2
*
1BD)
Sensor Connection
• When connecting directly to this module’s input circuit, be sure
to use a PNP output sensor.
You cannot connect directly via a 2-wire sensor or an NPN-type
sensor. For details about NPN-type sensor connections,
PRO-iO2 User Manual
(1)
1A Fuse (Fast-break type)
• Do not use negative voltages for the analog inputs. Doing so can
damage the internal circuit.
• The maximum length of the cable connected to an analog device
is 10 m.
(1)
1A Fuse (Fast-break type)
The following diagrams show an example of a PNP output sensor connection.
+ -
I1 I2 I3 I4 IB IC ID IE
+ -
I1 I2 I3 I4
ID IE IF IG - -
+ -
I1 I2 I3 I4 IB IC ID IE
Analog
Output
Device
Analog
Output
Device
Analog
Output
Device
Analog
Output
Device
24VDC
Blue
Black
Brown
Blue
Black
Brown
Main Circuit
24VDC
24VDC
0VDC to 10VDC analog
0VDC to 10 VDC analog
Blue
Black
Brown