Chapter 4 Installation and Wiring
4-9
Wiring
When connecting the Power Cord, use the following items when performing wiring. (Items are made by
Phoenix Contact.)
Connecting the Power Cord
(1)
Confirm that the power cord is unplugged from the power supply.
(2)
Remove the power connector (plug) from the main unit.
(3)
Strip the membrane of the power cord, twist the wire ends, and connect them to the Power Connector.
(4)
Reattach the Power Connector.
Recommended Driver
SZF 1-0.6x3.5 (1204517)
Recommended Pin
Terminals
AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)
Recommended Pin
Terminal Crimp Tool
CRIMPFOX ZA3 (1201882)
• Be sure to remove the connector from the ST unit prior to starting wiring. Failure
to do so may cause an electric shock.
• The temperature rating of field installed conductors: 75°C only.
• Use a flat-blade screwdriver (Size 0.6 X 3.5) to tighten the terminal screws.
The torque required to tighten these screws is 0.5 to 0.6N
•
m[5-7Lb
•
in].
• Do not solder the cable connection.
•
Be sure to twist the power cords together, up to the power connector.