![PRO AIR TPK 21 Скачать руководство пользователя страница 124](http://html1.mh-extra.com/html/pro-air/tpk-21/tpk-21_functional-description-and-operating-instructions_1603875124.webp)
RS 485 Interface
119
15.5.2. PIN-Belegung Stecker
121
Folgende PIN - Belegung gilt für die Anschlussstecker
Analog Interface 4….20 MA / 0…10 V
Pin
Colour
Alarm
Remarks
1
BN - brown
24 V
Operating voltage conn24 V DC
2
WH - white
RS_A
Signal line A
3
BU - blue
GND
Power supply earth
4
BK - black
RS_B
Signal line B
5
GN/YE green/yellow GNB
Signal earth
The RS 485 interface is not electrically isolated from the supply earth!
To supply power to the device, a mains adapter can be connected to Pin 1 (+) and Pin 2 (-)
Pin
Colour
Alarm
Remarks
1
BN - brown
24 V
Operating voltage conn24 V DC
2
WH - white
RS_A
Voltage output 0…10 V
3
BU - blue
GND
Power supply earth
4
BK - black
RS_B
Current output 4…20 mA
5
GN/YE green/yellow GNB
Signal earth
The analogue interface is not electrically isolated from the supply earth!
The current output is active, i.e. it delivers the signal current to earth and requires no
external supply
The voltage output is also active, i.e. it delivers the signal voltage to earth.
To supply power to the device, a mains adapter can be connected to Pin 1 (+) and Pin 3 (-)