10.3. Configuration of lower analog output value
88
The analogue output signal is freely configurable. Both the lower and the upper output value
can be freely determined.
The menu item
„Setpoint 4 mA/0V"
allows you to enter the
lower value
for the analog output
signal. The desired value must lie within the setting range selected in section 10.2.
If the
„Setpoint 4mA/0V“
field is not already highlighted, select the field and
confirm with .
The following screen will appear:
Select the desired value and confirm with
„Enter“
X
0,00
1
2
3
4
5
6
-
7
8
9
0
.
X
Source
Current / Voltage
Setpoint 4mA/0V
Setpoint 20mA/10V