HYSTER.
(hysteresis) This value will maintain the output on until the
process value falls under the set point - hysteresis value.
OFFSET
An offset value can be added or subtracted to bring the display
value to zero at atmospheric pressure. If you are using a
submersible pressure transducer, the level readout at atmos-
pheric pressure (out of the wet well) should be zero. If it is
not, add or subtract (negative) a value to bring the display to
zero. Check the level readout to verify if it is zero. If not, try to
change the offset again.
LAG
TMR
Delay timer before starting lag pump. Set from one second
to
600
seconds.
SEAL FLT
LED ONLY / LOCKOUT / LAG ONLY
LED ONLY:
In the event of a seal failure, the pump will still be
allowed to run and the seal fail light will turn on.
LOCK OUT:
Pump will not be allowed to run and light will turn on.
LAG ONLY:
Pump with a seal fail is only allowed to run in a lag
situation. Seal fail light will turn on.
THERMAL
AUTO RST / MANUAL
AUTO RST:
The pump will shut down on over temperature, but will
be allowed to run again if the pump cools down and the
fault
clears.
MANUAL:
The pump will shut down on over temperature and will
not be allowed to run until the fault clears and the
RESET button is pressed by the operator.
FIGURE 5
PRIMEX™ 14 SP6R-LSC Level Controller User Manual