background image

 HYSTER. 

(hysteresis)  This value will maintain the output on until the  

 

   

 

process value falls under the set point - hysteresis value.

 OFFSET 

 

An offset value can be added or subtracted to bring the display  

   

 

value to zero at atmospheric pressure.  If you are using a    

   

 

submersible pressure transducer, the level readout at atmos- 

   

 

pheric pressure (out of the wet well) should be zero.  If it is    

   

 

not, add or subtract (negative) a value to bring the display to  

   

 

zero.  Check the level readout to verify if it is zero.  If not, try to  

   

 

change the offset again.

 LAG 

TMR 

Delay timer before starting lag pump.  Set from one second 

 

 

  to 

600 

seconds.

 

 

SEAL FLT

 

LED ONLY / LOCKOUT / LAG ONLY

 

 

LED ONLY:

  In the event of a seal failure, the pump will still be

 

   

 

allowed to run and the seal fail light will turn on.

 

 

LOCK OUT:

  Pump will not be allowed to run and light will turn on.

 

 

LAG ONLY:

  Pump with a seal fail is only allowed to run in a lag

 

   

 

situation.  Seal fail light will turn on.

 

THERMAL 

AUTO RST / MANUAL

 

 

AUTO RST:

  The pump will shut down on over temperature, but will 

 

   

 

be allowed to run again if the pump cools down and the 

 

 

  fault 

clears. 

 

 

MANUAL:

 

The pump will shut down on over temperature and will

 

   

 

not be allowed to run until the fault clears and the 

 

   

 

RESET button is pressed by the operator.

FIGURE 5 

 

PRIMEX™                                                                                            14                                                               SP6R-LSC Level Controller User Manual

Содержание SP6R-LSC

Страница 1: ...L BAR GRAPH 4 20 mA INPUT AUTOMATIC AL TERNATION MOTOR STATUS LEDs User Manual SP6R LSC CONTROLLER Ashland OH 800 363 5842 Clearwater FL 800 349 1905 Detroit Lakes MN 888 342 5753 Milford OH 513 831 9...

Страница 2: ...ns Electrical Connections 8 10 8 10 Function Keys Displays Function Keys Displays 11 11 Setting Up Levels and Simulation Setting Up Levels and Simulation 11 12 11 12 Configuration Configuration 13 15...

Страница 3: ...indication Form C SPDT contacts rated at 10A at 240 VAC LEVEL DISPLAY Eight character alpha numeric LED for process value and program parameters POWER 24 VDC 10 200 mA nominal 400 mA max OPERATING TE...

Страница 4: ...figured for pump down or pump up applications SP6R LSC LEVEL CONTROLLER INTRODUCTION The standard SP6R LSC lift station controller kit contains see Figure 2 on page 5 of this manual one SP6R LSC lift...

Страница 5: ...Disconnect power before installing or servicing this product A qualified service person must install and service this product according to applicable electrical codes EXPLOSION OR FIRE HAZARD Do not...

Страница 6: ...emp High Level Lag Pump Lead Pump Low Level FIGURE 1 Dimensions and panel cut out Dimensions are indicative and may be subject to change without notification INSTALLATION DIMENSIONAL DATA PRIMEX 5 SP6...

Страница 7: ...PRIMEX 6 SP6R LSC Level Controller User Manual PANEL CUT OUT TEMPLATE FOR SP6R LSC LIFT STATION CONTROLLER 8 6 218 mm 4 7 16 112 mm cut along dotted line...

Страница 8: ...FIGURE 2 Standard SP6R LSC duplex lift station controller kit INSTALLATION DIMENSIONAL DATA PRIMEX 7 SP6R LSC Level Controller User Manual...

Страница 9: ...is pro tected with an overall shield connect the shield to terminal 3 Terminal 4 and 5 must be connected if an output follower is not required If no valid input is present the controller will flash SE...

Страница 10: ...FIGURE 6 Loop Powered Transducer Connection FIGURE 7 Self Powered Signal Connection PRIMEX 9 SP6R LSC Level Controller User Manual...

Страница 11: ...240 VAC fuse protection is required indi vidually or as a group Motor starters auxiliary contacts Thermal switches in motor winding Normally closed open on over temperature Seal fail contact from seal...

Страница 12: ...nger active NOTE The display automatically returns to level after 20 seconds of inactivity regardless of where it was left Pressing once will increment the current value by one unit Pressing and holdi...

Страница 13: ...ETTING UP LEVELS FIGURE 8 Example of how to move from level display screen LO LEVEL Low level alarm set point STOP LD Stop lead pump level set point STOP LAG Stop lag pump level set point STAR LD Star...

Страница 14: ...Percentage NONE Blank No Units Displayed When you are at the item you wish to edit press the ENTER key and the original value for the item selected will flash Use the UP and DOWN arrow keys to change...

Страница 15: ...r before starting lag pump Set from one second to 600 seconds SEAL FLT LED ONLY LOCKOUT LAG ONLY LED ONLY In the event of a seal failure the pump will still be allowed to run and the seal fail light w...

Страница 16: ...the corresponding output relay and it will remain ON until the level drops below the set point the PUMP mode is used for pump down or emptying applica tions In PUMP mode the relays turn ON as the leve...

Страница 17: ...lo0alarm 0000mode 0run0sig res0ctrs FIGURE 9 Use the arrow keys to navigate through these menu items NOTE Eight 8 seconds of inactivity no keys pressed will terminate the con figuration menu and exit...

Страница 18: ...OOFFSET 99 9 999 9 0 0 FT OLAGOTMR 1 0 600 3 0 SEC SEALOFLT OTHERMAL HIOALARM LOOALARM OOOOMODE PUMPXX PUMPXX PUMPXX ORUNOSIG USED UNUSED UNUSED RESOCTRS 0 0 0 CONFIGURATION MODE PARAMETERS FT IN CM M...

Страница 19: ...5 0 FT STAROLAG 0 0 999 9 6 0 FT HIOLEVEL 0 0 999 9 7 0 FT ALTERNAT AUTO OETM1OHR READ ONLY OETM2OHR READ ONLY OOOOOEC1 READ ONLY OOOOOEC2 READ ONLY SIMULATE RUN MODE PARAMETERS LEVEL DISPLAY 4 mA va...

Страница 20: ...controller can be configured for pump up or pump down applications Applications include level monitoring pressure temperature flow and analytical NEMA 4X The SP6R Set Point Controller is also availab...