background image

ADJUSTING TEMPERATURE 

SETPOINTS (TK-HC, TK-C)

The TK-HC Therma-Fuser diffuser is factory set for 

74° F/28°C for both heating and cooling. Because heat 

loads in various rooms differ and individual occupants 

prefer different temperatures, it is recommended that the 

thermostats should not be adjusted until after a few days of 

operation. 
Room temperature set points are adjusted by screwing 

the thermostats in or out – in for cooler or out for warmer. 

Determine the set point by aligning the white indicator with 

the °F or °C numbers on the temperature scale (See 

Fig. 6

).

The thermostats may be slightly harder to screw in or out 

when warm because the shaft is extended, putting more 

pressure on the thermostat. If you are unable to turn the 

thermostat in this situation, cool the thermostat by holding 

an ice cube to the large end. The shaft will then contract and 

the thermostat will turn easily for adjustment. 

BLOW PATTERNS (TK-HC, TK-C, TK-D)

A major selling feature of the TK-HC diffusers is the ability 

to easily add or remove blow patterns in the field. This is 

done by blocking the air off behind the blades on the  

appropriate sides.

DO NOT:

— Disconnect the spokes.

— Tape, screw or otherwise lock the blade closed. 

     This unbalances the loads on the center bearings.

— Block the venturi nozzle.

DO

 block air flow behind the blades or between the  

standoffs. (Standoffs are the supports between the  

housing and the diffusion plate.) Ways to do this are:
1. Factory installed directional baffles. These are strips of

metal wrapped around the standoffs to block one, two

or three sides. These can be removed in the field after

first removing the diffusion plate assembly.

2. Field installed directional baffles. These are made of

1-1/8”/ 28.575mm diameter x 5-5/8”/143mm long

insulation (Armaflex) for 3/8”/ 9.525mm refrigeration

lines. Insert between the housing and the diffusion

plate/blade assembly and wedge between the standoffs

(See Fig. 7). Take care to clear the damper hinges so

that the damper operates freely.

The rule for blocking the appropriate side is: 

Always block 

the side adjacent to the thermost.

 (See 

Fig. 8 

for examples.)

When blocking for direction, reduce maximum air volume 

for a given static pressure and throw in the performance 

guide by:

Blow Patterns 

Reduction

3 way (D3) 

.80

2 way opposite (D2) 

.64

2 way corner (D2C) 

.59

1 way (D1) 

.45

Fig 7. Field installed foam baffle

Page 3 of 6

Fig 6. Room temperature set point adjustment

RECOMMENDED ADJUSTMENTS FOR

VARIOUS CONDITIONS

Thermostats

Read setpoints here

Adjust cooling for higher room temperature set point. 

(Screw cooling thermostat out.)
Therma-Fuser diffuser is correct. Check if cooling is 

still required, and if not, turn cooling unit off.
Therma-Fuser diffuser is correct. Check for lack of 

air or for too warm air temperature.
Adjust cooling thermostat for lower room tempera-

ture set point. (Screw cooling thermostat in.)
Therma-Fuser diffuser is correct. Check for lack of 

air or too low air temperature.
Adjust heating thermostat for higher room tempera-

ture set point. (Screw heating thermostat out.)
Adjust heating thermostat for lower room tempera-

ture set point. (Screw heating thermostat in.)
Therma-Fuser diffuser is correct. Check if heating is 

still required, and if not, turn it off.
Reduce static pressure. Recommended static pres-

sure is .05 to .25 wg / 10 to 60 Pa at the inlet of the 

diffuser. If lower noise level does not result from 

lower static pressure, check for and correct noise 

generating restrictions in the duct up stream such as 

large pressure drops over dampers, heaters, etc. 

Open

Closed

Open

Closed

Open

Closed

Open

Closed

Any

Too

Cold

Too

Warm

Too

Cold

Too

Warm

Any

Cooling

Mode

TK-HC

Heating

Mode

TK-HC

Too

Noisy

TK-HC

TK-D

Room 

Temp.

Blade

Position

Recommended

Action

THERMA-FUSER

DIFFUSER

Diffusion

Damper

Housing

Probe

Appearance

Panel

Gauge

1250 to 

2300 fpm

Figure 7 @ 200%

Figure 3 @200%

Содержание Acutherm THERMA-FUSER SYSTEMS

Страница 1: ... 5 Ten Year Warranty 6 4 If other than 4 way blow pattern is factory installed note the AIRFLOW markings on the top of the diffuser and locate those sides in the proper direction 5 Install in ceiling grid Install T bar support wire close to each corner of diffuser Make sure that only wire suspended T bars are used to support diffuser weight Adaptor frames are available for other ceilings 6 Connect...

Страница 2: ... sensor for static pressure controller Measure supply return and branch duct air flow 4 Place a direct reading diffuser balancing hood over the face of each Therma Fuser diffuser and adjust damper at duct takeoff to obtain maximum design air volume If a velocity meter is used measure discharge velocity at the housing See Fig 3 Multiply the velocity in fpm times Ak of 12 ft2 to get air flow in cfm ...

Страница 3: ...en the housing and the diffusion plate blade assembly and wedge between the standoffs See Fig 7 Take care to clear the damper hinges so that the damper operates freely The rule for blocking the appropriate side is Always block the side adjacent to the thermost See Fig 8 for examples When blocking for direction reduce maximum air volume for a given static pressure and throw in the performance guide...

Страница 4: ... temperature limit should be as low as possible These objectives are best achieved by modulating chilled water valves hot water valves and other variable equipment from supply air temperature On off equipment such as DX compressors and electric heat are cycled from supply air temperature Use a discharge air sensor for the supply air temperature signal Mode change between heating recirculation and ...

Страница 5: ... temperature may vary over time several measurements at different times may be required 1 Room temperature 4 feet above the floor directly under the Therma Fuser diffuser 2 Supply air temperature at the Therma Fuser diffuser 3 Static pressure at the inlet of the Therma Fuser diffuser Thermostats Read setpoints here Measure from induction housing to edge of slider Cooling mode 7 8 in 22 mm Heating ...

Страница 6: ...and found defective and provided the diffusers have been given normal and proper usage and all parts and controls remain unaltered Acutherm makes NO WARRANTY OF MERCHANTABILITY OF PRODUCTS OR OF THEIR FITNESS FOR ANY PURPOSE OR ANY OTHER EXPRESS OR IMPLIED WARRANTY WHICH EXTENDS BEYOND THE LIMITED WARRANTY ABOVE ACUTHERM S LIABILITY FOR ANY AND ALL LOSSES AND DAMAGES RESULTING FROM DEFECTS SHALL I...

Отзывы: