![Price Industries Limited ECM Series Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/price-industries-limited/ecm-series/ecm-series_troubleshooting-manual_1599822013.webp)
11
priceindustries.com
|
ECM Motor - troubleshooting Manual
ECM MOTOR
TROUBLESHOOTING
FIGURE 6 - ECM STANDARD SPEED CONTROLLER -
CONTROL CABLE PINOUT
SPEED CONTROLLER END OF CONTROL CABLE
Pin 1 – 9 - 30 VDC “GO” SIG (White)
Pin 2 – Common (Black)
Pin 3 – Common (Green)
Pin 4 – 9 - 30 VDC “PWM” SIG (Red)
MTR1
MTR2
NOTE:
There are two motor output jacks (MTR1 & MTR2). They
are in parallel so either one can be used. Both jacks are used
on dual blower units.
Left to right, 1, 2, 3, 4
NOTE:
If colors are different than shown here, ensure wires are
still going to correct position.
MOTOR END OF CONTROL CABLE
White (1)
Black (2)
Green (3)
Red (4)