background image

Dwg. 105133 Page 1 

Calibration & Setup Procedure for ITC-79-FTF 

(includes ITC-79-FTF-BUF & ITC-79-FTF-DIV)

 

 

1. Factory Settings: 

(unless otherwise specified at time of order) 

 

ITC-79-FTF:

 

Input Type: Voltage Input, TTL level (0-5 VDC) (jumper H2-8 inserted) 
Thresholds: ON: TP1 = 3V  ,  OFF: TP2 = 1V 
Relay & 24V Pulse: Follows input directly (jumper H4-1 installed) 
Response Time: 100 microsec. (jumper H2-2 installed) 
TTL Output: Follows input directly (jumper H4-4 installed) 

 

ITC-79-FTF-BUF:

 

Input Type: Voltage Input, TTL level (0-5 VDC) (jumper H2-8 inserted) 
Thresholds: ON: TP1 = 3V  ,  OFF: TP2 = 1V 
Relay & 24V Pulse: Buffered pulse output (jumper H4-2 installed) 
Response Time: 100 microsec. (jumper H2-2 installed) 
TTL Output: Buffered pulse output (jumper H4-5 installed) 
Output Pulse Rate: 500 msec. 

 

ITC-79-FTF-DIV:

 

Input Type: Voltage Input, TTL level (0-5 VDC) (jumper H2-8 inserted) 
Thresholds: ON: TP1 = 3V  ,  OFF: TP2 = 1V 
Relay & 24V Pulse: Divided Output (jumper H4-2 installed) 
Response Time: 100 microsec. (jumper H2-2 installed) 
TTL Output: Divided Output (jumper H4-5 installed) 
Division Factor: 100

 

 
2. Input Type:

 

 

Determine the type of input that is to be applied to the ITC-79-FTF (choices are 

Voltage, Dry Contact, AC or DC Coupled 

).  Follow the instructions below depending 

on which input type you are using: 
 

Voltage Input:

 

 
Several input ranges for various voltage levels can be set up by jumpers H2-5 
through H2-8.  Select only one range and insert only one jumper for that range. 
 

 

0-10 mV 

insert jumper H2-5 

 

0-100 mV 

insert jumper H2-6 

 

0-1 V  

insert jumper H2-7 

 0-10 

V  insert 

jumper 

H2-8 

 

 

 

Dry Contact Input:

 

 

Insert  jumper H3 to select a 10 KOhm input impedance.  Insert jumper H2-8 to 
select a 0-10 V input  range.  Set  the ON threshold to +10 V (using TP1) and 
the OFF threshold to +5 V (using TP2). 
 

 

AC or DC Coupling:

 

 

The ITC-79-FTF is set up for DC Coupling by default.  To change the input to 
AC Coupling, remove jumper J1 and replace it with a 1 uF capacitor. 

 
 

3. Input Response Time:

 

 

There are four response times to choose from for the input conditioning circuitry.  
These response times help eliminate noise on the input signal.  Choose a response 
time that is adequate for your particular frequency input.  Make sure that the 
highest frequency that is to be accepted by the input has a period greater than the 
chosen response time.   
 

10 msec 

insert jumper H2-4 

Содержание ITC-79-FTF Series

Страница 1: ...alled Relay Function Frequency to Frequency Isolator Option ITC 79 FTF Power If special or required BUF Frequency Pulse Buffer Response Time 100 microsec DIV Frequency Divider Input 0 10 VDC Threshold...

Страница 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Страница 3: ...iturn potentiometers All potentiometers have a test point where a voltage of 10 to 10 VDC indicates the threshold level as 100 to 100 This allows for easy field calibration with the instrument running...

Страница 4: ...Outputs TTL 24VDC Dry Contact Function Store Pulses Release Slowly Dimensions Calibration Calibration is made easy by multi turn potentiometers with test jacks for meter connection Connection Manufact...

Страница 5: ......

Страница 6: ......

Страница 7: ...ut Type Determine the type of input that is to be applied to the ITC 79 FTF choices are Voltage Dry Contact AC or DC Coupled Follow the instructions below depending on which input type you are using V...

Страница 8: ...e ON and OFF threshold levels The ON and OFF LED s indicate which portion of the pulse is currently being received on frequencies above 30 Hz both LED s appear to be on simultaneously In the above exa...

Страница 9: ...1 The release time is encoded in binary which means that up to 65536 216 combinations of release rates are selectable Jumper position H1 1 is equivalent to 0 1 msec position H1 2 equals 0 2 msec H1 3...

Страница 10: ...ows H1 1 out H1 5 out H1 9 in H1 13 out H1 2 out H1 6 in H1 10 in H1 14 out H1 3 out H1 7 in H1 11 out H1 15 out H1 4 in H1 8 in H1 12 out H1 16 out The jumpers that are inserted carry the binary weig...

Страница 11: ......

Отзывы: