f. Open-circuit and short-circuit trouble of T4
g. High temperature protection of condenser
High temperature protection of condenser
Check the resistance of the temp. sensor
according to Annex 1, is it normal?
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is
defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
6. Outdoor PCB is defective
Replace the sensor
No
Yes
Is connection to connector of temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Is it the resistance is normal?
Indoor PCB is defective.
Replace the sensor
Yes
No
Содержание PAC247C-I
Страница 5: ......
Страница 9: ......
Страница 14: ...Service Space MLCAC UTSM 2011 02 12 Four way Cassette 3 Service Space 1000mm 1000mm 1000mm 1000mm ...
Страница 15: ...MLCAC UTSM 2011 02 Wiring Diagrams Four way Cassette 13 4 Wiring Diagrams PAC247C I PAC367C I ...
Страница 16: ...Wiring Diagrams MLCAC UTSM 2011 02 14 Four way Cassette PAC487C I ...
Страница 21: ...MLCAC UTSM 2011 02 Field Wiring Four way Cassette 19 8 Field Wiring Wiring chart PAC247C I PAC367C I ...
Страница 25: ...MLCAC UTSM 2011 02 Service Space Ceiling Floor Type 23 3 Service Space ...
Страница 26: ...Wiring Diagrams MLCAC UTSM 2011 02 24 Ceiling Floor Type 4 Wiring Diagrams PAC366FC I ...
Страница 27: ...MLCAC UTSM 2011 02 Wiring Diagrams Ceiling Floor Type 25 PAC486FC I PAC606FC I ...
Страница 32: ...Outdoor Units MLCAC UTSM 2011 02 30 Outdoor Units 9 Field Wiring PAC366FC I PAC486FC I PAC606FC I ...
Страница 35: ...MLCAC UTSM 2011 02 Features Outdoor Units 33 2 Service Space ...
Страница 37: ...MLCAC UTSM 2011 02 Features Outdoor Units 35 4 Wiring Diagrams PAC247C O ...
Страница 38: ...Features MLCAC UTSM 2011 02 36 Outdoor Units PAC367C O PAC366FC O ...
Страница 39: ...MLCAC UTSM 2011 02 Features Outdoor Units 37 PAC487C O PAC486FC O ...
Страница 40: ...Features MLCAC UTSM 2011 02 38 Outdoor Units PAC606FC O ...