33
Packaged and Split Rooftop Ventilator
© 2021 Mitsubishi Electric US, Inc.
Premi
Sys
Start-Up Checklist - Packaged Direct Expansion (DX)
Compressor 1 Compressor 2 Compressor 3 Compressor 4
L1
Amps
Amps
Amps
Amps
L2
Amps
Amps
Amps
Amps
L3
Amps
Amps
Amps
Amps
Crankcase Heater
Not present on inverter compressor
Amps
Amps
Amps
Amps
Superheat
(Housing 0-1, 1-1, 2-1, 4-1)
Should be between 8º and 12ºF
Deg. F
Deg. F
Deg. F
Deg. F
Subcooling
0-1, 1-1, 2-1, 4-1)
Should be between 8º and 12ºF
Deg. F
Deg. F
Deg. F
Deg. F
Superheat
(Housing 5)
Should be between 10º and 20ºF (0% reheat) or
should be between 10º and 30ºF (100% reheat)
Deg. F
Deg. F
Deg. F
Deg. F
Subcooling
(Housing 5)
Should be between 10º and 15ºF (0% reheat) or
should be between 2º and 10ºF (100% reheat)
Deg. F
Deg. F
Deg. F
Deg. F
Discharge Pressure
Should be between 300 and 500 PSIG
PSIG
PSIG
PSIG
PSIG
Suction Line Pressure
Should be between 100 and 135 PSIG
PSIG
PSIG
PSIG
PSIG
Liquid Line Temp.
Deg. F
Deg. F
Deg. F
Deg. F
Suction Line Temp.
Deg. F
Deg. F
Deg. F
Deg. F
Moisture Indicating Sight Glass
Liquid Visible
Yes / No
Yes / No
Yes / No
Yes / No
Color of Center Dot
Purple / Pink
Purple / Pink
Purple / Pink
Purple / Pink
Hot Gas Bypass Operational
Yes / No / NA
NA
NA
NA