Alarm Cards
1-25
Alarm Cards
Alarm Card User Screens and Settings
Table 1-5. ALR 28+14 Alarm Switch Screen Actions
Table 1-6. ALR 28+14 Alarm Switch Option Settings and Defaults
Notes:
1. Sensor numbers are assignable only if the ACT ON parameter is set to sensor number
1
to
28
. The default setting is
1
.
SWITCH NAME
A user-defined field up to six characters identifies the specific switch. Note that the switch
name is a local identifier; it is not transmitted with alarm conditions.
SW. CTRL
This variable indicates the initial state of the switch. The possibilities are
off
(which
unconditionally turns the switch off),
on
(which unconditionally turns the switch on) or
act_on
(which relies on the state of the switch). The default value is
off
.
As mentioned previously, 12 of the switches are Form C (which may be either open or closed),
one is Form A (always open), and one is Form B (always closed).
In the event of system power failure, switch 1 can be used as a fail-safe switch to activate a
device that notifies the user. In order for this to occur, a jumper must be set on jumper pair
JP63. located towards the center of the card. The contact for switch 1 will close if the system
loses power, establishing a circuit that can be used to power an external warning device. The
current source must be provided by the external device.
Action
Function
Refresh
Updates certain time-related information fields that are not automatically
updated.
dEfault
Returns all settings to the default states.
pgUp
Returns to the previous page.
pgDn
Goes to the next page.
Main
Returns to the Alarm Sensor Screen.
Parameter
User Options
Notes
Default
#
Alarm Switch number 1 to 14
fixed
SWITCH Name
User-defined switch name
blank
SW. CTRL
off on act_on
act_on
ACT ON
info minor major crit sensor
major
SENSOR #
n/a 1 to 28
1
n/a
STATUS
off on
displayed