Alarm Cards
1-19
Alarm Cards
Alarm Card User Screens and Settings
1.3
Alarm Card User Screens and Settings
1.3.1
Alarm Filter Screen Sensor Setting
First, make sure the master setting for all alarm sensors is set properly as the SENSOR variable
in the Alarm Filter Screen. To set this variable, first select
Alarms
from the System Main
Screen, then choose
Filters
. This will display a list of alarm filters, as shown in Figure 1-8.
In this menu, use the arrow keys to highlight the first column of the SENSOR line. Pressing
<Enter> displays the options
ignore
,
log
, and
report
. The option chosen here will act as the
highest-level option for all alarm card sensors. If this variable is set to
ignore
,
any alarm
conditions on the alarm card will be ignored
, even if you set them up individually to
log
or
report
.
Likewise, if you set this variable to
log
, all sensors on the Alarm card that are set to anything
other than
ignore
will be logged but not reported. For this reason, it is crucial that the
SENSOR variable be set to
report
(see Figure 1-8).