PD6830 Pulse Input Rate/Totalizer Instruction
Manual
35
Manual or Automatic Total Reset Function (
t rST
)
For manual reset, select
PROGRAM
t rst
man
and then next select whether
manual reset will be enabled (
Enabl
) or disabled (
dsabl
) using the up arrow key and
by then pressing the Enter/Ack button to accept. Disabling reset will avoid
inadvertent resets of the total via the front reset button or external reset contact.
For automatic reset, select
PROGRAM
t rst
Auto
T DELAY
and enter reset
delay time in seconds. Once the set point is reached, the meter waits for a
programmed amount of time (
T DELAY
) and then resets the total to zero.
The meter may be automatically reset based on the value programmed in the
Advanced menu:
INDICAT
alrm
total
SEt.
Press the Enter/Ack button, at any time, to accept a setting; otherwise press the
Menu button to exit without saving changes.
t rst
SeTUP
nman
T RESET
Auto
T RESET
Enter Reset Delay
(seconds)
0
0010
T DELAY
enabl
MAN RST
DSABL
MAN RST