PD6801 Explosion-Proof Loop-Powered Feet & Inches Level Meter
Instruction Manual
7
Product Ratings and Approvals
FM
Explosion-proof for use in:
Class I, Division 1, Groups B, C and D
Dust-ignition proof for use in:
Class II/III, Division 1, Groups E, F and G;
T6
Flame-proof for use in:
Class I, Zone 1, AEx d Group IIC; T6
Protection by Enclosure:
Zone 21, AEx tb IIIC; T85°C
Ta = -40 to 75°C.
Enclosure: Type 4X, IP66.
Certificate number: 3040391
CSA
Explosion-proof for use in:
Class I, Division 1, Groups B, C and D
Dust-ignition proof for use in:
Class II/III, Division 1, Groups E, F and G;
T6
Flame-proof for use in:
Zone 1, Ex d IIC T6
Ta = -40 to 75°C.
Enclosure: Type 4X & IP66/IP68.
Certificate number: 2325749
ATEX
II 2 G D. Flame-proof for use in:
Zone 1, Ex d IIC T6 Gb
Protection by Enclosure for use in:
Dust Atmospheres (Zone 21)
Ex tb IIIC T85°C Db IP68.
Ta = -40°C to +75°C
Certificate number: Sira 10ATEX1116X
IECEx
Flame-proof for use in:
Zone 1, Ex d IIC T6 Gb
Protection by Enclosure for use in:
Dust Atmospheres (Zone 21)
Ex tb IIIC T85°C Db IP68.
Ta = -40°C to +75°C
Certificate number: IECEx SIR 10.0056X
Special Conditions for Safe Use:
Use suitably certified and dimensioned cable entry
device and/or plug. The equipment shall be installed
such that the supply cable is protected from
mechanical damage. The cable shall not be subjected
to tension or torque. If the cable is to be terminated
within an explosive atmosphere, then appropriate
protection of the free end of the cable shall be
provided.
Year of Construction:
This information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
For European Community:
The PD6801 must be
installed in accordance with the ATEX directive
94/9/EC, and the product certificate Sira
10ATEX1116X.
Electromagnetic Compatibility
Emissions
EN 61326
Safety requirements for measurement,
control, and laboratory use
– Industrial
Group 1 Class A ISM emissions
requirements
Radiated
Emissions
Class A
Immunity
EN 61326
Safety requirements for measurement,
control, and laboratory use
ESD
±4 kV contact, ±8 kV air
RFI
–
Amplitude
Modulated
80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)
EFT
±2 kV DC mains, ±1 kV other
Telco Surge
±1 kV
CRFI
3 V, 0.15-80 MHz, 1 kHz 80% AM