PD6801 Explosion-Proof Loop-Powered Feet & Inches Level Meter 

Instruction Manual 

 

10

 

Cover Jam Screw 

The cover jam screw should be properly installed 
once the meter has been wired and tested in a safe 
environment. The cover jam screw is intended to  
prevent the removal of the meter cover in a 
flameproof environment without the use of tools. 
Using a M2 hex wrench, turn the screw clockwise until 
the screw contacts the meter. Turn the screw an  
additional 1/4 to 1/2 turn to secure the cover.  
Caution: Excess torque may damage the threads 
and/or wrench. 

Connections 

To access the connectors, remove the enclosure 
cover and unscrew the two captive screws that fasten 
the display module. Disconnect the ribbon cable and 
remove the display module. Signal connections are 
made to a four-terminal connector in the base of the 
enclosure. Grounding connections are made to the 
two ground screws provided on the base 

– one  

internal and one external.  
 

 

4-20 mA signal input positive 
terminal connection 

SIGNAL -

 

4-20 mA signal return/negative 
terminal connection when not 
using loop powered backlight. 

BAC

 

+9-30 VDC when powering 
backlight from external supply. 

BACKLIGHT -

 

4-20 mA signal return/negative 
terminal when using the  
installed loop powered backlight 
or ground/negative when 
powering backlight from external  
supply. 

 

NPN open collector output  
positive. 

OUTPUT-

 

NPN open collector output 
negative. 

RESET +

 

Contact closure alarm 
acknowledge pull up to 3 VDC. 

RESET-

 

Contact closure alarm 
acknowledge ground/negative. 

 
Refer to 

Figure 3 

for terminal positions. 

 

 

Observe all safety regulations. Electrical wiring 
should be performed in accordance with all 
agency requirements and applicable national, 
state, and local codes to prevent damage to the 
meter and ensure personnel safety. 

 

Static electricity can damage sensitive 
components. 

 

Observe safe handling precautions for  
static-sensitive components. 

 

Use proper grounding procedures/codes. 

 

If the meter is installed in a high voltage 
environment and a fault or installation error 
occurs, high voltage may be present on any lead 
or terminal. 

 

 

Figure 3. Connector Board 

 

 

 

SAFE-TOUCH

BUTTONS

BACKLIGHT

POWER

UNLOCK

LOCK

LOOP

9-36 VDC

+ - + -

SIGNAL

BACKLIGHT

+ - + -

OUTPUT

RESET

Содержание Protex Pro PD6801

Страница 1: ...ously Display Mountable at 0 90 180 270 SafeTouchTM Through Glass Button Programming 20 Segment Tank Side Level Indicator Bargraph Open Collector Output Assignable to High or Low Alarm HART Protocol T...

Страница 2: ...All rights reserved Introduction The ProtEX F I PD6801 is a rugged explosion proof loop powered indicator specifically designed for level applications in hazardous areas or in the harshest environmen...

Страница 3: ...c ProtEX Approvals Overview The ProtEX Series carries extensive international approvals for hazardous areas https www predig com videos CTsNXQeRqTA ProtEX Enclosure Unique Features Learn about the uni...

Страница 4: ...Main Menu 14 Setting Up the Meter SETUP 15 Setting Numeric Values 15 Scaling the Meter SCaLe 16 Selecting Inch Fraction Display Mode FRACTN 16 Scaling the Tank Level Indicator PERCENT 16 Configuring t...

Страница 5: ...Dimensions Side Cross Section View 9 Figure 3 Connector Board 10 Figure 4 Connections without Backlight 11 Figure 5 Connections with Loop Powered Backlight 11 Figure 6 Connections with Externally Powe...

Страница 6: ...Mode Rejection 64 dB at 50 60 Hz Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept...

Страница 7: ...40 C to 75 C Certificate number IECEx SIR 10 0056X Special Conditions for Safe Use Use suitably certified and dimensioned cable entry device and or plug The equipment shall be installed such that the...

Страница 8: ...ld be performed only by trained service personnel Service requiring replacement of internal components must be performed at the factory Disconnect from supply before opening enclosure Keep cover tight...

Страница 9: ...y part is missing or the meter malfunctions please contact your supplier or the factory for assistance Pre Installed Conduit Plug The PD6801 is supplied with one pre installed conduit plug for install...

Страница 10: ...20 mA signal return negative terminal connection when not using loop powered backlight BACKLIGHT 9 30 VDC when powering backlight from external supply BACKLIGHT 4 20 mA signal return negative termina...

Страница 11: ...ledge connections are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 External Alarm Reset Acknowledge Connections...

Страница 12: ...n Operation To actuate a button press and remove one finger to the glass directly over the marked button area Remove finger to at least 4 inches away from the glass in between button activations SafeT...

Страница 13: ...he meter Right Reset Button Press the Right arrow button to reset the maximum or minimum value while it is being displayed see Up Display Button below Press the Right arrow button to move to the next...

Страница 14: ...h 1 8th Set display for 1 8th inch fractions PERCENT Percent Scale the tank indicator full and empty values 0 PCT 0 Percent Set the tank empty value 100 PCT 100 Percent Set the tank full value DISPLAY...

Страница 15: ...nges made to settings prior to pressing ENTER are not saved Press the MENU button during Programming Mode to return to the previous menu selections Setting Numeric Values The numeric values are set us...

Страница 16: ...ling of the meter The minimum span is 0 10 mA Scale Error Message SPN ERR If the minimum span is not maintained the meter will show a span error SPN ERR and revert to input 2 allowing the appropriate...

Страница 17: ...arate second scale of the input process variable This is configured in Volume Display Scaling VOLSCAL on page 19 Percent full height shows the percent full of the tank height level indicator programme...

Страница 18: ...Medium Set noise filter to medium setting HI Filter High Set noise filter to high setting OFF Filter Off Disable noise filter VOLSCAL Volume Scale Scale the volume display NO PTS Number of Set the nu...

Страница 19: ...lay and ALARM until the alarm condition is cleared The alarm status will show on the display even if the output is not wired Input Signal Filter FILTER The noise filter is available for unusually nois...

Страница 20: ...moment while the meter is accepting the signal After the signal is accepted the meter displays 20 mA Apply a 20 000 mA signal and press ENTER The display flashes for a moment while the meter is accept...

Страница 21: ...he meter will display the message LOCKED when the Menu button is pressed Press the Enter button while the message is being displayed and enter the correct password to gain access to the menu After exi...

Страница 22: ...played will reset that value to the current display value Press the DISPLAY button a third time and the meter will display LOOP MA on the lower display followed by the measured input current in millia...

Страница 23: ...nostics menu and consult the recommendations described below Troubleshooting Tips Symptom Check Action No display or faint display Check input signal connections Perform hard reset by shorting S and S...

Страница 24: ...selection or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms To enter the Advanced Features Menu hold the M...

Страница 25: ...8 655 8990 www predig com LIM6801_I SFT087 Ver 1 300 up 02 22 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call...

Отзывы: