ProtEX-MAX PD8-7000 Explosion-Proof Temperature Meter Instruction Manual
46
Programmable Function Keys User Menu (
user
)
The
User
menu allows the user to assign the front panel function keys F1, F2, and F3, the digital input F4
(a digital input located on the signal input connector), and up to eight additional digital inputs to access
most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states,
etc.). This allows the meter to be greatly customized for use in specialized applications.
Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter
(i.e. alarms, relay acknowledgement, reset max, min, or max & min, tare, and reset tare). The digital
outputs can be used to trigger external alarms or lights to indicate these specific events.
Function Keys & Digital I/O Available Settings
Refer to the following table for descriptions of each available function key or digital I/O setting.
Display
Description
Rst Hi
Reset the stored maximum display
value
Rst Lo
Reset the stored minimum display
value
Rst HL
Reset the stored maximum & mini-
mum display values
tare
Capture tare and zero the display
Rst tr
Reset captured tare and resume
normal operation
relay
Directly access the relay menu
Set 1
*
Directly access the set point menu
for relay 1 (*through 8)
Rly d
Disable all relays until a button as-
signed to
enable relays
(
Rly E
) is
pressed
Rly E
Enable all relays to function as they
have been programmed
O Hold
Hold current relay states as they
are until a button assigned to
ena-
ble relays
(
Rly E
) is pressed
d Hold
Hold the current display value mo-
mentarily while the function key or
digital input is active. The process
value will continue to be calculated
in the background.
Ln1 Hi
Display maximum display value on
line 1
Ln1 Lo
Display minimum display value on
line 1
Ln1 HL
Display maximum & minimum dis-
play values on line 1
Display
Description
Ln2 Hi
Display maximum display value on
line 2
Ln2 Lo
Display minimum display value on
line 2
Ln2 HL
Display maximum & minimum dis-
play values on line 2
F On 1
*
Force relay 1 (*through 4) into the
on state. This function is used in
conjunction with a digital input to
achieve interlock functionality. See
page 37 for details about interlock
relays.
Contrl
Directly access the control menu
disabl
Disable the selected function key or
digital I/O
AcH
Acknowledge all active relays that
are in a manual operation mode
such as auto-manual or latching
Reset
Directly access the reset menu
nmenu
Mimic the menu button functionality
(digital inputs only)
rigHt
Mimic the right arrow/F1 button
functionality (digital inputs only)
up
Mimic the up arrow/F2 button func-
tionality (digital inputs only)
Enter
Mimic the enter/F3 button function-
ality (digital inputs only)
Alnm 1
*
Provide indication when alarm 1
(*through 8) has been triggered
(digital outputs only)
*If installed