background image

PD6701 Field-Mount Loop-Powered Feet & Inches Level Meter 

Instruction Manual 

 

17

 

Alarm Output (

OUTPUT

The PD6701 is equipped with an NPN open collector 
output that may be set up for high or low alarm trip 
point based on the level display (

LEVEL

) or the volume 

scale (

VOLUME

). The output may be disabled by 

selecting 

OFF

When the alarm is enabled for level and the alarm set 
point has been reached, the level display will flash, 
accompanied by the lower display alternating 
between normal display and 

ALARM

. A tank height 

indicator segment will flash at the level the alarm is 
set to while the level indicator is at or above the alarm 
point. 
When the alarm is enabled for volume and the alarm 
set point has been reached, the lower display will 
flash, alternating between its normal display and 

ALARM

To set a high alarm, program the set point value to be 
greater than the reset point. 
To set a low alarm, program the set point value to be 
less than the reset point. 
To acknowledge an alarm, press the 

ENTER

 button 

once for acknowledge prompt and a second time to 
confirm. Acknowledging an alarm will turn off the 
alarm output and stop the display from flashing. The 
lower display will continue to alternate between its 
normal display and ALARM until the alarm condition is 
cleared. 
The alarm status will show on the display even if the 
output is not wired. 

 

 

 

Input Signal Filter (

FILTER

The noise filter is available for unusually noisy signals 
that cause an unstable process variable display. The 
noise filter averages the input signal over a certain 
period. The filter level can be set to low (

LO

), medium 

(

MED

), high (

HI

), or off (

OFF

). The higher the filter 

setting, the longer the averaging time and so the 
longer the display may take to find its final value. 
The filter contains a noise filter bypass feature so that 
while small variations in the signal will be filtered out, 
large, abrupt changes to the input signal are 
displayed immediately. 

 

Volume Display Scaling (

VOLSCAL

Volume may be scaled as a function of the feet and 
inches level display. It may use up to 32-point 
linearization. The multi-point linearization can be used 
to linearize the display for non-linear signals such as 
those from level transmitters used to measure volume 
in odd-shaped tanks. 

To display the volume, select a lower display 
including the volume display in the 

Display 

menu as 

shown in 

Configuring the Lower Display

 (

DISPLAY

on 

page 

14

. 

To scale the volume display, enter the level in feet 
and inches for input 1, and then the corresponding 
volume display value. Do the same for input 2. 
After entering the display 2 value, confirm the new 
volume scale by pressing 

ENTER

 at the 

Save

 menu. 

 

 

 

 

 

Содержание PD6701

Страница 1: ...Tag Volume or Percent Display Level in Feet Inches and Volume Percent or Decimal Height Simultaneously Display Mountable at 0 90 180 270 SafeTouchTM Through Window Button Programming 20 Segment Tank...

Страница 2: ...1 is a rugged field mount loop powered indicator specifically designed for level applications in harsh environmental conditions The meter displays level in easy to read and understand feet inches and...

Страница 3: ...es 12 Scaling the Meter SCaLe 13 Selecting Inch Fraction Display Mode FRACTN 13 Scaling the Tank Level Indicator PERCENT 13 Configuring the Lower Display DISPLAY 14 Setting the Tag TAG 14 Advanced Fea...

Страница 4: ...e Dimensions Side Cross Section View 6 Figure 3 Connector Board 7 Figure 4 Connections without Backlight 8 Figure 5 Connections with Loop Powered Backlight 8 Figure 6 Connections with Externally Power...

Страница 5: ...ower is lost Normal Mode Rejection 64 dB at 50 60 Hz Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Scre...

Страница 6: ...rt damages if any to the carrier If any part is missing or the meter malfunctions please contact your supplier or the factory for assistance Pre Installed Conduit Plug The PD6701 is supplied with two...

Страница 7: ...klight from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm ack...

Страница 8: ...nnections are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 External Alarm Reset Acknowledge Connections Open Co...

Страница 9: ...n Operation To actuate a button press and remove one finger to the window directly over the marked button area Remove finger to at least 4 inches away from the window in between button activations Saf...

Страница 10: ...meter Right Reset Button Press the Right arrow button to reset the maximum or minimum value while it is being displayed see Up Display Button below Press the Right arrow button to move to the next di...

Страница 11: ...1 8th Set display for 1 8th inch fractions PERCENT Percent Scale the tank indicator full and empty values 0 PCT 0 Percent Set the tank empty value 100 PCT 100 Percent Set the tank full value DISPLAY D...

Страница 12: ...es made to settings prior to pressing ENTER are not saved Press the MENU button during Programming Mode to return to the previous menu selections Setting Numeric Values The numeric values are set usin...

Страница 13: ...ng of the meter The minimum span is 0 10 mA Scale Error Message SPN ERR If the minimum span is not maintained the meter will show a span error SPN ERR and revert to input 2 allowing the appropriate in...

Страница 14: ...ate second scale of the input process variable This is configured in Volume Display Scaling VOLSCAL on page 17 Percent full height shows the percent full of the tank height level indicator programmed...

Страница 15: ...e Advanced features menu functions and messages in the order they appear in the menu Display Parameter Action Setting OUTPUT Output Enter output menu OFF Off Disable output ALARM Alarm Output Enter al...

Страница 16: ...ibration parameters ICAL Internal Calibration Enter internal reference calibration 4mA 4 mA Calibrate input at 4 mA 20mA 20 mA Calibrate input at 20 mA ERRSPAN Error Span Error with calibration point...

Страница 17: ...y and ALARM until the alarm condition is cleared The alarm status will show on the display even if the output is not wired Input Signal Filter FILTER The noise filter is available for unusually noisy...

Страница 18: ...ment while the meter is accepting the signal After the signal is accepted the meter displays 20 mA Apply a 20 000 mA signal and press ENTER The display flashes for a moment while the meter is acceptin...

Страница 19: ...meter will display the message LOCKED when the Menu button is pressed Press the Enter button while the message is being displayed and enter the correct password to gain access to the menu After exiti...

Страница 20: ...ayed will reset that value to the current display value Press the DISPLAY button a third time and the meter will display LOOP MA on the lower display followed by the measured input current in milliamp...

Страница 21: ...ostics menu and consult the recommendations described below Troubleshooting Tips Symptom Check Action No display or faint display Check input signal connections Perform hard reset by shorting S and S...

Страница 22: ...lection or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms To enter the Advanced Features Menu hold the Men...

Страница 23: ...655 8990 www predig com LIM6701_E SFT087 Ver 1 300 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 8...

Отзывы: