Model PD655 Large Display Process Meter
Instruction Manual
53
Setting Relays for Pump Alternation (
ALtERn
)
Setting relays for pump alternation control
At the end of the
SetuP
menu, the display will show
alternate (
ALtErn
), press
ENTER
to set up this function. If
ENTER
is not pressed within 3 seconds, this function will
remain programmed as it was before, and the next menu will
be displayed.
ALtErn
then
SetPtS
If
ENTER
is pressed while display reads
ALtErn
,
display changes to
Alt rY
, status LEDs 1-4 flash
in pairs. To program relay pair to alternate, press
ENTER
when desired pair is flashing. To program
relays for independent operation (not to alternate),
press
ENTER
when all status LEDs are off. After
making the selection,
Setpts
menu is displayed.
Possible combinations of alternating relays: 1-2,
1-3, 1-4, 2-3, 2-4, 3-4, and none.
Note: Only one relay pair can be set up to
alternate at a time.
AltErn
then
Alt rY
then
Select flashing
LED Pair
then
SetPtS
This completes the set points setup. The display moves to the next
programming menu,
SEtPtS
. Program the alarm set/reset and preset values.
To exit main programming menu and return to reading press the
ACK
button.