Model PD6000 Analog Input Process Meter Instruction Manual
27
Display Parameter
Action/Setting
Description
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-
cleared
Set relay for latching operation with ma-
nual reset only after alarm condition has
cleared
Altern
Alternate
Set relay for pump alternation control
Sampl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown, only if ex-
pansion relay module is installed.
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
break
Loop break
Set relay condition if loop break detected
ignore
Ignore
Ignore loop break condition
(Processed as a low signal condition)
On
On
Relay goes to alarm condition when loop
break is detected
Off
Off
Relay goes to non-alarm condition when
loop break is detected
Aout
Analog output
Enter the
Analog output
scaling menu
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value (e.g. 4.000 mA)