background image

Helios Large Display Dual Analog Input Rate/Totalizer Instruction Manual 

PD2-6262

 

 


 
 

Relay 
Operation 

Automatic (non-latching) and/or 
manual reset 
Latching (requires manual 
acknowledge) with/without clear 
Pump alternation control (2 to 4 
relays) 
Sampling (based on time) 
Off (disable unused relays and enable 
Interlock feature) 
Manual on/off control mode 

Relay Reset 

User selectable via front panel buttons 
or digital inputs 

 

1.  Automatic reset only (non-

latching), when the input passes 
the reset point. 

2. 

Aut manual reset at any 
time (non-latching) 

3.  Manual reset only, at any time 

(latching) 

4.  Manual reset only after alarm 

condition has cleared (latching) 

Note: Front panel button or digital 

input may be assigned to 
acknowledge relays 
programmed for manual reset. 

Time Delay 

0 to 999.9 seconds, on & off relay time 
delays  
Programmable and independent for 
each relay 

Fail-Safe 
Operation 

Programmable and independent for 
each relay.  

Note: Relay coil is energized in non-

alarm condition. In case of 
power failure, relay will go to 
alarm state. 

Auto 
Initialization 

When power is applied to the meter, 
relays will reflect the state of the input 
to the meter. 

Isolated 4-20 mA Transmitter Output 

Output 
Source 

Input channels A or B, rate, total, or 
grand total; channel C; max or min for 
channel A or B; highest or lowest max 
or min of A and B; set points 1-8; 
Modbus input; or manual control mode 

Scaling 
Range 

1.000 to 23.000 mA for any display 
range 

Calibration 

Factory calibrated: 4.000 to 20.000 = 
4-20 mA output 

Analog 
Output 
Programming 

23.000 mA maximum for all 
parameters: 
Overrange, underrange, max, min, 
and break 

Accuracy 

± 0.1% of span ± 0.004 mA 

Temperature 
Drift 

0.4 µA/

C max from 0 to 65

ambient,  
0.8 µA/

C max from -40 to 0

ambient

 

Note: Analog output drift is separate 
from input drift.

 

Isolated 
Transmitter 
Power 
Supply 

Terminals I+ & R: 24 VDC 

 10%. May 

be used to power the 4-20 mA output 
or other devices. Refer to Figure 21 
on page 19. 
All models rated @ 40 mA max.  

External 
Loop Power 
Supply 

35 VDC maximum 

Output Loop 
Resistance 

Power supply  Minimu

Maximum 

24 VDC 

10 

 

700 

 

 

35 VDC 
(external) 

100 

 

1200 

 

RS485 Serial Communications Terminal 

Compatibility 

EIA-485 

Connectors 

Removable screw terminal connector 

Max Distance 

3,937' (1,200 m) max 

Status 
Indication 

Separate LEDs for Power (P), 
Transmit (TX), and Receive (RX) 

Modbus

®

 RTU Serial Communications 

Slave Id 

– 247 (Meter address) 

Baud Rate 

300 

– 19,200 bps 

Transmit 
Time Delay 

Programmable between 0 and 199 ms 

Data 

8 bit (1 start bit, 1 or 2 stop bits) 

Parity 

Even, Odd, or None with 1 or 2 stop 
bits 

Byte-To-Byte 
Timeout 

0.01 

– 2.54 second 

Turn Around 
Delay 

Less than 2 ms (fixed) 

Note: Refer to the Modbus Register Tables located at 
www.predig.com for details. 

Digital Input & Output Terminal 

Channels 

4 digital inputs & 4 digital outputs 

Digital Input 
Logic High 

3 to 5 VDC 

Digital Input 
Logic Low 

0 to 1.25 VDC 

Digital 
Output Logic 
High 

3.1 to 3.3 VDC 

Digital 
Output Logic 
Low 

0 to 0.4 VDC 

Source 
Current 

10 mA maximum output current 

Sink Current 

1.5 mA minimum input current 

+5 V 
Terminal 

To be used as pull-up for digital inputs 
only.  
Connect normally open pushbuttons 
5 V & DI 1-4. 

 

WARNING!

 

DO NOT use 
+5 V terminal 
to power 
external 
devices. 

 

 

Содержание PD2-6262

Страница 1: ...to 65 C 40 to 150 F Dual Analog Inputs with Math Functions Rate Total and Grand Total for Each Input Channel Addition Difference Average Multiplication Division Min Max Weighted Average Ratio Concentr...

Страница 2: ...ld result in personal injury or property loss Anyone using this product for such applications does so at their own risk Precision Digital Corporation shall not be held liable for damages resulting fro...

Страница 3: ...ogramming Time Delay 38 Relay Action for Loss of 4 20 mA Input Loop Break 38 Relay and Alarm Operation Diagrams 38 High Alarm Operation Set Reset 38 Low Alarm Operation Set Reset 38 High Alarm with Fa...

Страница 4: ...features large 1 8 inch superluminous sunlight readable LED digits which can be read from up to 100 feet away It is housed in a water resistant field mountable IP65 rated enclosure for convenient ind...

Страница 5: ...nd total or grand total Ch A Ch B Relay set points Max and or min values Ch A Ch B or Ch C Toggle between any rate channel units Total and units Ch A or Ch B Toggle between totals Ch A Ch B Ch A Ch B...

Страница 6: ...s labor Dual Process Input Two Inputs Two non isolated inputs each separately field selectable 0 20 4 20 mA 10 V 0 5 1 5 0 10 V Modbus PV Slave Channels Channel A Channel B Channel C Math channel Math...

Страница 7: ...izer parameters programmed independently Totalizer Rollover Totalizer rolls over when display exceeds 999 999 999 Relay status reflects display Total Overflow Override Program total A or B total reset...

Страница 8: ...mA output Analog Output Programming 23 000 mA maximum for all parameters Overrange underrange max min and break Accuracy 0 1 of span 0 004 mA Temperature Drift 0 4 A C max from 0 to 65 C ambient 0 8...

Страница 9: ...ing screw Wires should be run through the knockout holes located on the bottom of the meter There are a total of four pre drilled conduit entry holes located at the bottom of the meter If the need to...

Страница 10: ...right on the wall 2 Using a drill bit slightly smaller than the girth of the mounting screws pre drill holes at the mounting locations previously marked 3 Insert mounting screws into the four mounting...

Страница 11: ...ng kit accessory follow these instructions 1 Secure the mounting plates to the top and bottom for vertical pipes or left and right for horizontal pipes of the reverse side of the meter enclosure using...

Страница 12: ...te the P P switch located in the center of the connections board see diagram below 4 Flip this switch into the appropriate position for the required transmitter excitation Figure 6 Transmitter Supply...

Страница 13: ...equipment and the meter Do not disconnect the RJ45 connector located to the left of the power terminal block Doing so will disable the onboard digital I O RS 485 serial communications and M Link func...

Страница 14: ...e no switches or jumpers to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 9 Transmitters Powered by Internal Supply Figure 10 Transmit...

Страница 15: ...ression can be obtained with resistor capacitor RC networks assembled by the user or purchased as complete assemblies Refer to the following circuits for RC network assembly and installation Figure 13...

Страница 16: ...2 485 converter in an RS 422 network Figure 16 shows the connection of several meters to a PC using a PDA7485 RS 232 to RS 422 485 converter in an RS 485 network When using more than one meter in a mu...

Страница 17: ...und shield only at one location Connections Figure 17 details the wiring connections from the RS 485 connector to an RS 422 485 serial converter such as the PDA7485 or PDA8485 for a four wire network...

Страница 18: ...appropriate digital input connector block and the 5 VDC block Digital output connections are made by wiring from the appropriate digital output block to the grounding terminal block Figure 19 Digital...

Страница 19: ...see page 45 In one example dry interlock contacts are connected in series to one digital input which will be used to force on energize the assigned interlock power relay when all interlock contacts ar...

Страница 20: ...liamps and volts depending on the input selection The calibration equipment is certified to NIST standards Overview There are no jumpers to set for the meter input selection Setup and programming are...

Страница 21: ...de Up arrow F2 A B C Channel displayed Acknowledge Enter F3 1 4 Flashing Relay interlock switch open Note F4 F8 are digital inputs Note LEDs for relays in manual mode flash with the M LED every 10 sec...

Страница 22: ...d double click on the drive labeled MAINSTAL 3 Double click on the file named MAStart The program will open a few windows and install two programs on your computer Simply follow the onscreen instructi...

Страница 23: ...decimal point channel A and B only Total Total Set total decimal point channel A and B only Gtotal Grand total Set grand total decimal point channel A and B only prog Program Enter the Program menu In...

Страница 24: ...al D rt b Display rate and total B Alternate display of channel B rate and total Drgt a Display rate and grand total A Alternate display of channel A rate and grand total Drgt b Display rate and grand...

Страница 25: ...d Set relay for latching operation with manual reset only after alarm condition has cleared Altern Alternate Set relay for pump alternation control Sanmpl Sampling Set relay for sampling operation OFF...

Страница 26: ...A grand total Gtot b Reset grand total B Press Enter to reset channel B grand total Tot ab Reset totals A and B Press Enter to reset channels A and B totals Gt ab Reset grand totals A and B Press Ent...

Страница 27: ...ved to memory only after pressing Enter F3 The display moves to the next menu every time a setting is accepted by pressing Enter F3 Setting Numeric Values The numeric values are set using the Right an...

Страница 28: ...B 2 Units for A B rate total grand total and C 3 Decimal positions for A B rate total and grand total and C 4 Program the meter using the scale calibrate total functions 5 Display parameters and inte...

Страница 29: ...selecting Yes or no after the input type has been set up for each channel If the totalizer features are disabled all the totalizer features and functions are hidden from the menus Level and process m...

Страница 30: ...Display Character 0 0 C C k K v V 1 1 c c l L u w w 2 2 d d m m x X 3 3 e E n n y Y 4 4 f F O O z Z 5 5 g G o o 6 6 9 g p P 7 7 H H q q 8 8 h h r r 9 9 I I s S A A I i t t Degree b b j J u u Space No...

Страница 31: ...al time base conversion factors 5 Channel A and B reset modes for total grand total The process inputs may be calibrated or scaled to any display value within the range of the meter Additional paramet...

Страница 32: ...icates that the calibration or scaling process was not successful After the error message is displayed the meter reverts to the input prior to the failure during calibration or scaling and to input 1...

Страница 33: ...32 Warm up the meter for at least 15 minutes before performing calibration to ensure specified accuracy The meter can be calibrated to display the process variable in engineering units by applying th...

Страница 34: ...wn independent settings This means that one can be displaying the value in gallons while the other displays in million gallons liters m3 etc Total Grand Total Reset Total reset menus are located in th...

Страница 35: ...sum of total A and total B d tABC Notes The sum of total A and B for t ABC is independent of channel C programming Channel C may be used normally by a different display selection even when D tABC is...

Страница 36: ...Modbus 2 Relay action a Automatic reset only non latching b Automatic manual reset at any time non latching c Latching manual reset only d Latching with Clear manual reset only after alarm condition h...

Страница 37: ...rnation control automatic reset only 6 Sampling the relay is activated for a user specified time 7 Off relay state controlled by Interlock feature The following graphic shows relay 1 action setup rela...

Страница 38: ...ss of 4 20 mA Input Loop Break The loop break feature is associated with the 4 20 mA input Each relay may be programmed to go to one of the following conditions when the meter detects the loss of the...

Страница 39: ...Operation Set Reset Note Relay coil is energized in non alarm condition In case of power failure relay will go to alarm state Low Alarm with Fail Safe Operation Set Reset Note Relay coil is energized...

Страница 40: ...Turn On Go to alarm condition 2 Turn Off Go to non alarm condition 3 Ignore Processed as a low signal condition Time Delay Operation The following graphs show the operation of the time delay function...

Страница 41: ...to the meter is off Front Panel LEDs The LEDs on the front panel provide status indication for the following The meter is supplied with four alarm points that include front panel LEDs to indicate alar...

Страница 42: ...ndition Latching Relay LatcH In this application the meter is set up for manual reset at any time Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off th...

Страница 43: ...off Application 1 Pump Alternation Using Relays 1 2 1 Relays 1 and 2 are set up for pump alternation 2 Relays 3 and 4 are set up for low and high alarm indication Pump Alternation Operation 1 Pump 1...

Страница 44: ...With the Pump Alternation feature activated the next time the level reaches 6000 gallons relay 3 transfers and starts the backup pump 3 If the backup pump is not able to keep up and the level reaches...

Страница 45: ...5V terminal and the corresponding digital input dI 1 to dI 4 terminal Interlock Relay Operation Example Relays 1 2 are configured to energize their front panel LEDs are off when SW1 SW2 switches above...

Страница 46: ...see Setting Numeric Values page 27 Reset Menu reset The Reset menu is used to reset the maximum peak value of Ch A and Ch B rate rst Hi minimum valley reading of Ch A and Ch B rate rst Lo both high a...

Страница 47: ...ion keys and digital inputs Total Prevents resetting the total manually Gtotal Prevents resetting the grand total manually Protecting or Locking the Meter Enter the Password menu and program a six dig...

Страница 48: ...password protection access the Password menu and enter the correct password twice as shown below The meter is now unprotected until a new password is entered If the correct six digit password is ente...

Страница 49: ...Channel B Set filter value for channel B bypASs Bypass Set filter bypass value Ch A Channel A Set filter bypass value for channel A Ch b Channel B Set filter bypass value for channel B Round Round Set...

Страница 50: ...on Channel C A A B F Sunm t Sum total C tA tB P F Sunmgt Sum grand total C GtA GtB P F Dif t Difference of total C tA tB P F Dif gt Diff of grand total C GtA GtB P F Tratio Total ratio C tA tB F T pct...

Страница 51: ...i Current high Calibrate high current input e g 20 mA v CAL Voltage calibration Calibrate voltage input v Lo Voltage low Calibrate low voltage input e g 0 V v Hi Voltage high Calibrate high voltage in...

Страница 52: ...ote More detailed instructions are provided with each optional serial communications adapter Note Refer to the Modbus Register Tables located at www predig com for details When using more than one met...

Страница 53: ...output transfer function applied to the input signal linear square root programmable exponent or round horizontal tank volume calculation Multi point linearization is part of the linear function selec...

Страница 54: ...s used to measure volume in odd shaped tanks or to convert level to flow using weirs and flumes with complex exponent Note After Scale is displayed continue pressing the Enter button until the meter c...

Страница 55: ...amming the cutoff value to zero disables the cutoff feature Totalizer Count Up Down Count The totalizer count up down menu may be used to program the total and grand total to either count up from 0 wh...

Страница 56: ...and program the output scale Programmable Function Keys User Menu user The User menu allows the user to assign the front panel function keys F1 F2 and F3 the digital input F4 a digital input located...

Страница 57: ...splay value on line 1 Ln1 HL Display maximum minimum channel A display values on line 1 Display Description Ln2 Hi Display maximum channel B display value on line 2 Ln2 Lo Display minimum Channel B di...

Страница 58: ...message C lo Apply the low input signal and press Enter The display flashes for a moment while the meter is accepting the low input signal 6 After the display stops flashing a number is displayed wit...

Страница 59: ...or math channel on the upper display and a unit or tag on the lower display The relays and analog output can be programmed to operate based on any input or math channel Button Operation Button Symbol...

Страница 60: ...The max min displays are reset to actual values 3 Press Menu to exit max min display reading Troubleshooting Due to the many features and functions of the meter it s possible that the setup of the met...

Страница 61: ...the factory setting for most of the programmable parameters on the meter Parameter Display Default Setting Input type Input Input type channel A Ch A 4 20 mA Input type channel B Ch B 4 20 mA Total ch...

Страница 62: ...og output Aout Display 1 analog out Dis 1 4 000 Output 1 value Out 1 4 000 mA Display 2 analog out Dis 2 20 000 Output 2 value Out 2 20 000 mA Source analog output Source Channel A Overrange output O...

Страница 63: ...tc Scaling or calibration Display does not respond to input changes reading a fixed number Check Display assignment it might be displaying max min or set point Display alternates between Hi and a numb...

Страница 64: ...ision Digital For Technical Support please Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com For Sales Support or to place an order please contact your local distributor or C...

Отзывы: