PD2-6262 Helios Large Display Analog Dual-Input Rate/Totalizer Instruction Manual
25
Display
Parameter
Action/Setting Description
D tab
Display total A and B
Alternate display of channel A total and channel B total
D TAbC
Display total A, B,
and math channel C
Alternate display of channel A total, channel B total, and math
result channel C
m bus
Display Modbus
Display Modbus input register
D off
Display off
Display blank little display
D unit
Display unit
Display big display channel units
d-Inty
Display intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the
Relay
menu
Assign
Assignment
Assign relays to channels or Modbus
Asign1
*
Assign 1
Relay 1 (*through 4) assignment
Ch-A
*
Channel A*
Assign relay to channel A (*or B, C)
m bus
Modbus
Assign relay to Modbus register
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Auto-manual
Set relay for automatic & manual reset any time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-cleared
Set relay for latching operation with manual reset only after
alarm condition has cleared
Altern
Alternate
Set relay for pump alternation control
Sanmpl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
break
Loop break
Set relay condition if loop break detected
ignore
Ignore
Ignore loop break condition (Processed as a low signal
condition)
On
On
Relay goes to alarm condition when loop break is detected
Off
Off
Relay goes to non-alarm condition when loop break is detected
Aout
Analog output
Enter the
Analog output
scaling menu
AOut 1
*
Aout channel
Analog Output source channel (*1
– 3)
Dis 1
Display 1
Program display 1 value