Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
22
Open Collector Outputs (
OPEN COLLECTR
)
The meter is equipped with two NPN open collector outputs that may be set up for pulse outputs, alarms,
timed pulses, total reset, or turned off.
Pulse outputs can be set to transmit the rate, total, or grand total. Output 2 may be used to generate a
quadrature output based on the other open collector output. An output test mode is also selectable to
generate pulses at a constant programmable frequency.
Alarms are available based on the PV value or the digital input. The alarm status will show on the display
even if the output is not wired.
A timer output turns the open collector on and off at a specified frequency to act as a timer.
A total reset output generates a pulse whenever the total is reset, regardless of the reset method used.
The On time is programmable between 0 and 9,999 seconds.
The output may be disabled by selecting
DISABLE
.
SETUP
OUTPUT
OPEN
COLLECTR
OC.OUT
OUTPUT1
OC.OUT
OUTPUT2
OUT 1
PULSE
PULSE
RATE
PULSE
QUAD
*Available
for output
2 only.
*
OUT 1
ALARM
OUT 1
TIMER
OUT 1
DISABLE
ALARM
RATE
ALARM
D.INPUT
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
MODE
CONT
MODE
ONE.SHOT
PULSE
TEST
OUT 1
TOT RST
TIME
0000 SEC
PULSE
TOTAL
PULSE
GTOTAL
ALARM
TOTAL
ALARM
GTOTAL