Helios Large Display Temperature Meter Instruction Manual
PD2-7000
30
Setting the Relay Action
Operation of the relays is programmed in the
Action
menu. The relays may be set up for
any of the following modes of operation:
1. Automatic reset (non-latching)
2. Aut manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Relay alternation (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-4 are set up in a similar
fashion.
Programming Set and Reset Points
High alarm indication: program set point above reset point.
Low alarm indication: program set point below reset point.
The deadband is determined by the difference between set
and reset points. Minimum deadband is one display count. If
the set and reset points are programmed with the same
value, the relay will reset one count below the set point.
Note: Changes are not saved until the reset point has been
accepted.