™ PD6363 Dual Analog Input Rate/Totalizer
Instruction Manual
45
Select Menu (
SElect
)
The
Select
menu is used to select the input signal conditioner applied to the inputs, math function for A & B,
constants, low-flow cutoff, total count direction (up or down from a preset amount), and analog output programming.
Multi-point linearization is part of the linear function selection.
Input Signal Conditioning (
Functn
)
The
Function
menu is used to condition the linear
input signal. Multi-point linearization is part of the
linear function selection. Each input channel input
signal conditioner is programmed independently.
Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with
2-point linearization. Up to 32 linearization points can
be selected for each channel under the linear
function. The multi-point linearization can be used to
linearize the display for non-linear signals such as
those from level transmitters used to measure volume
in odd-shaped tanks or to convert level to flow using
weirs and flumes with complex exponent.
Note: After Scale is displayed continue pressing the
Enter button until the meter completes the
scaling of the input and display values.