Application #2: Pump Alternation Using Relays 3 & 4
1. Relays 1 and 2 are set up for low and high alarm indication.
2. Relays 3 and 4 are set up for pump alternation.
Set and Reset Point Programming
Relay Set Point Reset Point
Function
1
495
750
Controls low alarm
2
7500
6900
Controls high alarm
3
7000
900
Controls backup pump
4
6000
1000
Controls main pump
The following graphics provide a visual representation of a typical pump alternation application with high
and low alarm monitoring:
•
Relay #4 turns the main pump on at 6000
gallons and turns it off at 1000 gallons.
•
With the Pump Alternation feature
activated, the next time the level reaches
6000 gallons, relay #3 transfers and
starts the backup pump.
•
If the backup pump is not able to keep
up, and the level reaches 7000 gallons,
relay #4 transfers and starts the main
pump as well.
•
Relay #2 trips the High Level Alarm at
7500 gallons and resets at 6900 gallons.
•
Relay #1 trips the Low Level Alarm at
495 gallons and resets at 750 gallons.