ProtEX-MAX PD8-6100 Strain Gauge, Load Cell, and mV Meter
Instruction Manual
50
Advanced Features Menu
To simplify the setup process, functions not needed
for most applications are located in the
Advanced
Features
menu.
Press and hold the Menu button for three seconds to
access the advanced features of the meter.
Advanced Features Menu &
Display Messages
The following table shows the functions and
messages of the
Advanced Features
menu in the
order they appear in the menu.
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
filtEr
Filter
Set noise filter value
bypASs
Bypass
Set filter bypass value
Round
Rounding
Select rounding value
seriAl
Serial
Set serial communication
parameters
SlaveId
Slave ID
Set slave ID or meter
address
baud
Baud rate
Select baud rate
Tr dLY
Transmit delay
Set transmit delay for serial
communication
Parity
Parity
Select parity
Even, Odd, or None with 1
or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu
(function, cutoff, out)
Functn
Input signal
conditioning
Linear, select number of
points
Linear
Linear
Set meter for linear
function and select number
of linearization points
PV 1
PV1
Select PV1 number of
linearization points
PV 2
PV2
Select PV2 number of
linearization points
No PtS
Number of
points
Set PV1 for 2 to 32-point
linearization
Set PV2 for 2 to 8-point
linearization
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
SCALE
Scale
Scaling parameter
SCAL 1
Scale 1
Scaling parameter 1
SCAL 2
Scale 2
Scaling parameter 2
CutofF
Cutoff
Set low-value cutoff
Auto 0
Auto Zero
Enter the Auto Zero
function (on/off)
AoutPr
Analog output
programming
Program analog output
parameters
Source
Source
Select source for the
4-20 mA output
O-rang
Overrange
Program mA output for
display overrange
u-rang
Underrange
Program mA output for
display underrange
nmAx
Maximum
Program maximum mA
output allowed
nmin
Minimum
Program minimum mA
output allowed
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 nmA
4 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
20 nmA
20 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
user
User I/O
Assign function keys and
digital I/O
F1*
F1 function key
Assign F1 function key
(*F1/F2/F3)
F4
F4 function
Assign F4 function
(digital input)
dI I
Digital input 1
Assign digital input 1
– 4
dO 1
Digital output 1
Assign digital output 1
– 4
ICal
Internal source
calibration
Enter internal source
calibration (used for
scaling the meter without a
signal source)
15nmV
15 mV
calibration
Calibrate 15 mV input
range (internal reference
source used for scaling the
input)
20nmV
20 mV
calibration
Calibrate 30 mV input
range (internal reference
source used for scaling the
input)
100nmV
100 mV
calibration
Calibrate 150 mV input
range (internal reference
source used for scaling the
input)