background image

www.predig.com

4

PD6620 Series 

Loop Leader

 

Loop-Powered Rate/Totalizers

Predefined and Custom Units

The meter has six available preprogrammed unit classes, 

volume

height

,

 temperature

,

 pressure

,

 weight

, and 

rate

. When the desired 

unit class or unit of measure within a class is not available, a custom 

unit may be programmed by using the (

CUSTOM

) menu.

Change Between Units without Needing to  

Re-Scale the Meter

It is possible to change the display units within the selected unit class 

without the need to re-scale the meter. When selecting a new unit 

from within the 

DISPLAY

 menu (e.g. changing from gallons (

GAL

) to

liters (

L

)), the meter will automatically convert the display values to 

display the new unit. If entering a custom unit (

CUSTM

), a custom 

conversion factor will need to be entered.

OUTPUTS

Loop Leaders are available with two open collector outputs as 

standard and two solid state relays and 4-20 mA output as options. 

The open collector outputs and relays generally operate in the 

same manner, with the major exception being the open collectors 

are not available for batch control or sampling and the relays are 

not available with pulse features. The open collectors and relays 

can be controlled either automatically or manually. The alarm status 

(with flashing red message) will show on the display even with no 

output wired.

Two Open Collector Outputs 

The Loop Leader is equipped with two NPN open collector outputs 

that may be set up for pulse outputs, alarms, timed pulses, stopwatch 

on/off, or disabled. Pulse outputs can be set to transmit the rate, total 

or grand total. Output 2 may be used to generate a quadrature output 

based on the other open collector output. An output test mode is also 

selectable to generate pulses at a constant programmable frequency. 

The open collectors are commonly used to generate a pulse for every 

user-defined amount of flow that has been generated. For instance, 

the Loop Leader can be programmed to generate a pulse for every 

100 gallons of flow.

Two Optional Solid State Relays 

The meter is optionally equipped with two solid state relays that may be 

set up for alarms, timer, stopwatch on/off, sample or batch control. The 

relays are rated at 250 VAC/DC @ 1 A for resistive loads and 75 VA @ 

0.6 A, 250 VAC/DC max (Safe Area only) for inductive loads. Alarms 

are available based on the rate, total, grand total, or digital input.

Resetting the Open Collectors and Relays  

The open collectors and relays (alarms) may be programmed to reset 

in the following ways:

•  

Automatic

 (

AUTO

): Alarm will reset automatically once the alarm 

condition has cleared.

•  

Automatic/Manual

 (

AUTO.MAN

): Alarm will reset automatically 

once the alarm condition has cleared but can also be reset using 

the Enter button (or whichever function key is set to acknowledge) 

at any time.

•  

Latching

 (

LATCH

): Alarm must be reset manually and can be 

done so at any time. Press the Enter (ACK) button at any time to 

clear the alarm. 

•   

Latching with Reset after Cleared

 (

L-CLEAR

): Alarm must be 

reset manually and can only be done so after the alarm condition 

has cleared. Press the Enter (ACK) button after the alarm 

condition has cleared to reset the alarm.

Timer Function Application

Application Timers are used in everyday life; one of the most common 

examples is the microwave oven. Industrial timers are used in 

process control applications where certain events or actions need to 

be controlled by time. Examples include automatic and batch control 

applications, where the relay needs to be energized for a specific 

length of time.
The timer fuction is available on the open collector and relay outputs; 

which means that you can have up to four timers per meter. The start 

and stop actions can be triggered from the setup menu or by the 

function keys and digital input. The meter can be setup to display the 

off/on timer count down.
There are two modes of operation:

1. Continuous Timer (Interval)

At the start of the timer the output is off and turns on after the 

Off Delay elapses. The output remains on for the duration of the 

On Time. The cycle repeats until the user stops the timer either 

from the menu or a function key.

2. One-Shot Timer

At the start of the timer the output is off and turns on after the  

Off Delay elapses. The output remains on for the duration of the  

On Time. The timer stops and the cycle does not repeat.

a.

  A sensor detects the bottle is in place and triggers the digital 

input to start the timer

b.

 The timer output controls the filling pump

c.

  The On Time is set according to the time needed to fill the bottle 

Optional Isolated 4-20 mA Output

The isolated analog output signal can be configured to represent 

the rate, total or to retransmit the 4-20 mA signal input without the 

need to scale the output. While the output is nominally 4-20 mA, the 

signal will accurately accommodate under- and over-ranges from 1 

to 23 mA. The output can be reverse scaled such that the meter’s 

high calibration value outputs 4 mA and the meter’s low calibration 

outputs 20 mA.

Sampling Relay 

A relay set to sample will trigger when the total or grand total value 

has incremented by a programmed amount. The relay can be 

programmed to stay on for a specified amount of time. For example: 

if a relay is set to sample the total with a COUNT of 1,000 and a TIME 

of 10 seconds, the relay will energize for 10 seconds each time the 

total increments by 1,000 (e.g. 1000, 2000, 3000).

Содержание PD6620 Series

Страница 1: ...oth Lines 20 Segment Bargraph with Numeric Percent Indication Conformal Coated PCBs for Dust Humidity Protection Two Open Collector Outputs Standard Dual Line Display 1 8 DIN Shallow Depth Case Optional Loop Powered Solid State Relays Optional 4 20 mA Analog Output UL C UL 61010 Listed for Electrical Safety UL C UL Listed as Intrinsically Safe and Nonincendive ATEX and IECEx Certified as Intrinsic...

Страница 2: ...ns can be used as function keys In addition a digital input is standard and is particularly useful for remote reset of the total or to start stop a timer batch All models come equipped with two open collector outputs and are available with two solid state relays and 4 20 mA analog output options The open collector outputs are useful for alarm indication or sending a pulse to indicate when a certai...

Страница 3: ...p Leader s flashing red alarm message can be activated even if no relay or open collector is connected Dual Scale Display Feature Users can use the Loop Leader s dual scale feature when they want to show the same input in two different scales For instance the following example shows an application where the Loop Leader displays the input in gallons per minute and cubic feet per minute Rate in GPM ...

Страница 4: ...tomatic Manual AUTO MAN Alarm will reset automatically once the alarm condition has cleared but can also be reset using the Enter button or whichever function key is set to acknowledge at any time Latching LATCH Alarm must be reset manually and can be done so at any time Press the Enter ACK button at any time to clear the alarm Latching with Reset after Cleared L CLEAR Alarm must be reset manually...

Страница 5: ...open The barrel begins to fill Preclose Valve When the batch total reaches a value of 50 00 Preset 55 00 Preclose 5 00 the full flow valve closes The fill rate of the tank slows as a result Completed Batch When the batch total equals the preset amount the restricted flow valve closes The barrel is now full Change Preset After placing a new empty barrel a new preset fill amount may be selected with...

Страница 6: ...the user can also program time delays and fail safe operation Multi Point Linearization Meters are set up at the factory for linear function with 2 point linearization Up to 32 linearization points can be selected for the scaled value under the linear function Multi point linearization can be used to linearize the display for non linear signals to convert level to flow using weirs and flumes with ...

Страница 7: ...y Flow Rate and Total at the same time Set upper display for Grand Total and lower display to toggle between rate and total Sampling Take a 1 pint sample every 100 000 gallons Set up relay for sampling and to trip every 0 1 million gallons Set up sampling time such that 1 pint is sampled Preset 0 100 100 000 gallons 0 100 Relay LED Total 0 200 0 300 Sample Time Sample Time Sample Time Total Relay ...

Страница 8: ... 20 mA Connections The following figures show a 4 20 mA loop connected to the meter The first figure shows the connection without the backlight and the second shows the connection with the backlight The meter is powered by the 4 20 mA current loop 4 20 mA Input Connection without Backlight 4 20 mA Input Connection with Backlight I I Power Supply Device with 4 20 mA Input Safe Area 4 20 mA Output C...

Страница 9: ...lues are stored in non volatile memory for a minimum of ten years if power is lost Normal Mode Rejection 64 dB at 50 60 Hz Connections Removable screw terminals accept 12 to 22 AWG DI Digital Input Contacts 2 1 VDC on contact Connect normally open contacts across DI and DI DI Digital Input Logic Levels Logic High 2 4 to 30 VDC max Logic Low 0 to 0 9 VDC Tightening Torque Screw terminal connectors ...

Страница 10: ...f when stopped Open Collector Outputs Rating Two NPN Isolated open collector 5 30 VDC 150mA max Output Assignment Pulse Alarm Timer Total Reset Stopwatch on off or Disable Pulse Output Source Rate Total Grand Total or Test Frequency Pulse Output Factor 0 000001 to 999 999 9 Pulse Width 0 5 ms 1 kHz 500 ms 1 Hz 50 duty cycle Pulse Output Frequency 1 000 Hz maximum Quadrature Pulse Output Available ...

Страница 11: ...dow is used to The 4 20 mA Output window is used to program the isolated 4 20 mA output s source range and under and over range values Function THIS METER Set the input 4 20 mA Enable disable the totalizer Totalizer enabled Enable disable the dual scale feature Dual scale disabled Scale the input Linear input unit is gallons 2 cal points 4 20 mA 0 100 GAL Free PC Based USB Programming Software Eas...

Страница 12: ...inted Steel NEMA 4 Enclosure PDA2801 Low Cost Plastic NEMA 4X Enclosure PDA3407 Internally Mount NEMA 4X Plastic Enclosure PD6620 Series Loop LeaderLoop Powered Rate Totalizers LDS6622_G 08 18 www predig com Precision Digital Corporation 233 South Street Hopkinton MA 01748 USA Tel 800 343 1001 Fax 508 655 8990 Loop Leader PD6622 Standard Decimal Models General Purpose Model Description PD6622 LNN ...

Отзывы: