Model PD6363 Pulse Dual-Input Rate/Totalizer Instruction Manual
80
Signal Input Conditioning (
Functn
)
The
Function
menu is used to condition the linear input signal. Multi-
point linearization is part of the linear function selection. Each input
channel signal input conditioning function is programmed independently.
Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with 2-point
linearization. Up to 32 linearization points can be selected for each
channel under the linear function. The multi-point linearization can be
used to linearize the display for non-linear signals such as those from
level transmitters used to measure volume in odd-shaped tanks or to
convert level to flow using weirs and flumes with complex exponent.
Note: After Scale is displayed continue pressing the Enter button
until the meter completes the scaling of the input and display
values.