PD500

 SuperNova PID Process & Temperature Controllers

www.predig.com

13

Temperature Inputs

Temperature Input Selection: 

Field programmable for 

thermocouple or RTD

Thermocouple Type:

 K, J, E, T, R, B, S, L, N, U, W, PLII

RTD Type:

 JPT100, PT100

Cold Junction Compensation:

 (RJC) ±1.5°C (-10 to  50°C)

RTD Max Line Resistance:

 Three wire RTD with identical line 

resistance up to 10 Ω

Input Sampling: 

20 samples/sec (50 ms per sample). For display 

update rate, see 

Display Update Rate

Input Accuracy:

Input 

Type

Prog  

No 

Display

Scale Range

Accuracy

K

1

K0

-328 to 2498°F

-200 to 1370°C

±0.2% of FS

± 1 digit

2

K1

-148 to 932°F

-100.0 to 500.0°C

J

3

J0

-328 to 2192°F

-200 to 1200°C

4

J1

-328 to 1652°F

-199. To 900.0°C

E

5

E1

-328 to 1652°F

-199.9 to 900.0°C

T

6

T1

-328 to 752°F

-199.9 to 400.0°C

R

7

R0

32 to 3092°F

0 to 1700°C

B

8

B0

212 to 3272°F

100 to 1800°C

±0.2% of FS

± 1 digit

100 to 200°C:

±2.0% of FS

± 1 digit

S

9

S0

32 to 3092°F

0 to 1700°C

±0.2% of FS

± 1 digit

L

10

L1

-328 to 1652°F

-199.9 to 900.0°C

N

11

N0

-328 to 2372°F

-200 to 1300°C

U

12

U1

-328 to 752°F

-199.9 to 400.0°C

W

13

W0

32 to 4172°F

0 to 2300°C

PLII

14

PL0

32 to 2372°F

0 to 1300°C

JPt100

20

JPt0

-328 to 932°F

-200 to 500°C

21

JPt1

-328 to 932°F

-199.9 to 500.0°C

Pt100

22

Pt0

-328 to 1184°F

-200 to 640°C

23

Pt1

-328 to 1184°F

-199.9 to 640.0°C

Control Outputs

Control Outputs: 

Each controller has a main control output and 

a secondary control relay output for two directions of control. The 

secondary control relay output is always used for On/Off operation.

Main Control Output:

 4-20 mA output (SCR), voltage pulse (SSR), 

or electromechanical relay (On/Off) outputs available.

Control Type: 

ON/OFF, PID control

Output Operation:

 Programmable for reverse or direct action.

Current SCR Output:

 4-20 mA linear current output

Load resistance: 600 Ω maximum

± 0.2% of FS ± 1 digit

Voltage Pulse SSR Output:

 12 V ± 1 VDC

Load resistance: 600 Ω minimum

Recommended minimum cycle time: 1 sec

Relay Output:

 Rated resistive load switching capacity:

5 A, 250 VAC; 5 A, 30 VDC

Max switching power: 750 VA, 90 W

Max switching voltage: 250 VAC, 110 VDC

Max switching current: 5 A

Mechanical life: 20 million cycles (at 180 CPM)

Recommended minimum cycle time: 20 sec

Alarm Relay Outputs

Function: 

Programmable for 13 different alarm types or off.

Number: 

Two alarm relays standard on all models.

Alarm Relay Ratings:

 Rated resistive load switching capacity:

5 A, 250 VAC; 5 A, 30 VDC

Deadband:

 0-100% FS, user selectable

High or Low Alarm:

 User may program any alarm for high, low, 

or high-low range operation.

Absolute or Deviation Alarm:

 User may program any alarm as an 

absolute value alarm or a set value deviation alarm.

Loop Break Alarm:

 User may program any SUB alarm relay as a 

loop break alarm.

Alarm Relay Operation:

• Automatic (non-latching) and/or manual reset 

• Latching (requires manual acknowledge) with/without clear 

• Off (disable unused relays)

Relay Reset (Acknowledge):

 Automatic, front panel button, in 

setup parameter menu, or through serial communications.

Time Delay: 

0 to 999 seconds, on and off delays; programmable for 

each SUB relay.

Fail-Safe Operation:

 Programmable, independent for each alarm 

relay. Relay coils are energized in non-alarm condition. In case of 

power failure, relays will go to alarm state.

Standby Operation: 

Programming, independent for each alarm 

relay

Auto

 

Initialization: 

When power is applied to the controller, relays 

will reflect the state of the input to the controller unless standby 

mode is enabled.

4-20 mA Retransmit Output

Function: 

4-20 mA linear current output

Scaling Range:

 0-100% of full scale

Output Loop Resistance:

 600 Ω maximum load

Output Accuracy:

 ±0.2% of full scale ± 1 digit

0-10 VDC Output:

 The PD659-1MA-1V can convert the optional 

4-20 mA output to a 0-10 VDC output

Remote SV Process Input

Function: 

Process input to remotely change SV

Input Type & Range: 

1-5 V, 4-20 mA

External 250 Ω resistor required to read 4-20 mA.

Input Accuracy: 

±0.2% of full scale ± 1 digit

Содержание PD510

Страница 1: ...and Heating Cooling Control Primary Control Output Options 4 20 mA SCR Voltage Pulse SSR or Relay Secondary Control Output Relay Standard on All Models Easily Switch Between Auto and Manual Control Modes Up to 2 Alarm Relays 4 20 mA Retransmit Outputs Remote Set Value 1 5 V Input Option 4 20 mA with External Resistor Digital Input Set Value Selection RS 485 Serial Communications Option Modbus RTU ...

Страница 2: ...ig com 2 TABLE OF CONTENTS OVERVIEW 3 EASY TO READ OPERATE 4 QUICK SETUP PROGRAMMING 4 PROCESS TEMPERATURE INPUTS 5 VERSATILE OPERATION 5 SUPERNOVA TCS SOFTWARE 7 NEMA 4 4X FIELD ENCLOSURES 8 DIMENSIONS 9 CONNECTIONS 10 SPECIFICATIONS 11 ORDERING INFORMATION 14 ...

Страница 3: ...to retransmit the process variable set value or output level This is especially useful for temperature inputs like thermocouples and RTDs Other options include a secondary 4 20 mA input to remotely control the set value and RS 485 for Modbus communication A mini USB port may be used for a direct PC connection to run the SuperNova software for monitoring programming and data logging This USB port i...

Страница 4: ...ped by category To access the group menus press and hold the Mode MD button for one second Navigate through the group menus using the UP or DOWN arrow buttons To enter a Group or change a parameter press SET Group Display Group Name General Description Set Value Group Select active Set Values and Set Value limits Input Group Configure input type and display scaling Output Group Configure control o...

Страница 5: ... two alarm relays two digital inputs serial communications and remote setpoint control make the SuperNova an excellent choice for any process or temperature control application requiring easy to change visible set points Main Control Secondary Outputs The main control output can be a 4 20 mA SCR voltage pulse SSR or relay output A secondary relay control output is standard which allow for one or t...

Страница 6: ...ons ability PDA7485 PDA8485 Analog Retransmit Output An optional 4 20 mA retransmitting output is available on all sizes of SuperNova Controllers This is especially useful when using a temperature input to provide a 4 20 mA signal to the control room or other equipment 4 20 mA Retransmitting Output Retransmit Based on PV SV or MV Auto Tuning PID A high accuracy auto tuning function calculates the ...

Страница 7: ...rd drive Data log files may be exported to HTML xls xlsx or pdf format as graphs or data tables Graphs may also be exported as bmp gif jpeg or png Data tables may also be exported as csv USB Powered USB port provides power to the controller for programming Apply normal power for general controller operations Remote Programming SuperNova TCS software allows all setup parameters to be programmed rem...

Страница 8: ...ontroller wiring Enclosures are available for 1 2 PD510 1 6 PD520 or 1 2 PD530 SuperNovas The enclosure is large enough to mount the PDA1024 01 DIN rail mounted 24 V transmitter supply Plastic Enclosures Internally Mounted PDA3400 Series Covers with screws The PDA3400 Series enclosures for the SuperNova fully cover the controller The controller is fully housed inside the enclosure behind a clear p...

Страница 9: ... 1 6 PD520 SuperNovas PDA2606 V with Six PD520s 1 8 DIN PDA2601 V with One PD520 1 8 DIN Steel Enclosures Externally Mounted PDA2700 Series Covers with Hinge Latch This is Precision Digital s painted steel line of enclosures for the SuperNova The controller mounts through a hinged cover with a latch allowing for easy access to controller wiring Enclosures are available for 1 6 PD520 SuperNovas PDA...

Страница 10: ...t s provided with the controller Insert controller into the panel cutout Install mounting bracket s and tighten the screws against the panel To achieve a proper seal tighten the mounting bracket screws evenly until controller is snug to the panel DO NOT OVER TIGHTEN as the rear of the panel may be damaged See Figure 1 and Figure 2 Figure 1 PD510 Mounting Bracket Installation Figure 2 PD520 PD530 M...

Страница 11: ...5 26 27 28 29 30 31 32 33 34 35 36 13 14 15 16 17 18 19 20 21 22 23 24 See Manual SUB1 SUB2 COM RLY RLY OUT1 OUT2 RTD mA V B A B TC RS485 A B SCR or SSR RLY 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 OUT2 RLY OUT1 RET REM RTD B A B TC mA V RS485 A B D I 1 COM D I 2 SUB1 SUB2 COM RLY RLY See Manual RLY PD510 R 1 16 DIN PD520 R 1 8 DIN PD530 R 1 4 DIN RET D I 1 COM D I 2 REM 1 2 3 4 5 6 7 8 9 10 1...

Страница 12: ...520 0 81 20 5 0 50 12 8 0 37 9 3 PD530 1 14 29 0 0 59 15 0 0 43 11 0 PV Display Update Rate 4 second 250 ms Non Volatile Memory Settings stored for a minimum of 10 years EEPROM life 1 million writes Included Components Controller with rubber gasket and mounting bracket 250 Ω resistor 1 and Quick Start Guide Additional 250 Ω resistor 1 provided for models with remote setpoint input option EEPROM Lo...

Страница 13: ...ce 600 Ω minimum Recommended minimum cycle time 1 sec Relay Output Rated resistive load switching capacity 5 A 250 VAC 5 A 30 VDC Max switching power 750 VA 90 W Max switching voltage 250 VAC 110 VDC Max switching current 5 A Mechanical life 20 million cycles at 180 CPM Recommended minimum cycle time 20 sec Alarm Relay Outputs Function Programmable for 13 different alarm types or off Number Two al...

Страница 14: ...ange 3 937 ft 1 2 km Baud Rate Programmable for 4800 9600 14400 19200 38400 57600 bps Start Bit 1 bit Data Bits Programmable for 7 or 8 bits Parity Programmable for none even or odd Stop Bit Programmable for 1 or 2 bits Protocol PC LINK STD PC LINK SUM MODBUS ASCII MODBUS RTU Response Time Actual response time processing time response time x 50 ms SuperNova TCS Software Availability Download direc...

Страница 15: ...elays 100 240 VAC PD520 S CTD Voltage Pulse SSR Relay Control Output 2 Alarm Relays RS 485 4 20 mA Retransmit 2 Digital Inputs 100 240 VAC PD520 S CTDR Voltage Pulse SSR Relay Control Output 2 Alarm Relays RS 485 4 20 mA Retransmit 2 Digital Inputs 4 20 mA SV Input 100 240 VAC PD520 R Relay On Off Relay Control Output 2 Alarm Relays 100 240 VAC PD520 R CTD Relay On Off Relay Control Output 2 Alarm...

Страница 16: ...2 Relay output for On Off control 2 SUB alarm relay outputs R Control OUT 1 Relay output for On Off or time proportional PID control Control OUT 2 Relay output for On Off control 2 SUB alarm relay outputs S Control OUT 1 Voltage pulse output for On Off or time proportional SSR PID control Control OUT 2 Relay output for On Off control 2 SUB alarm relay outputs Communication RS485 None C RS 485 comm...

Страница 17: ...1MA 1MA Signal Isolator with One 4 20 mA Input and One 4 20 mA Output PD659 1MA 2MA Signal Splitter with One 4 20 mA Input and Two 4 20 mA Outputs PD659 1V 1MA Signal Conditioner with One 0 10 VDC Input and One 4 20 mA Output PD659 1MA 1V Signal Conditioner with One 4 20 mA Input and One 0 10 VDC Output Your Local Distributor is Model Series Controllers Material Enclosures for PD510 1 16 DIN Contr...

Отзывы: