PD500

 SuperNova PID Process & Temperature Controllers

www.predig.com

12

Process Inputs

Process Input Selection: 

Voltage or current (with included external 

resistor)

Process Input: 

1-5 V (4-20 mA), 0-5 V, 0-10 V, 0-50 mV, 0-100 mV

External 250 Ω resistor required to read 4-20 mA. Recommended 

accessory PDX-RES2.

Decimal Point: 

Up to 3 decimals.

Input Sampling:

 20 samples/sec (50 ms per sample). For display 

update rate, see 

Display Update Rate

Input Accuracy:

Input Type Prog  No 

Display

Scale 

Range

Accuracy

4-20 mA*

30

1-5

-1999 to 

9999

±0.2% of FS

± 1 digit

1-5 V

30

1-5

0-5 V

31

5V

0-10 V

32

10V

0-50 mV

33

0.05V

0-100 mV

34

0.1V

* To achieve the highest accuracy with a 4-20 mA input to the 

controller, connect a 250 Ω (0.1% or higher precision) resistor 

across the input terminals. The 250 Ω (1%) resistor included with 

the product is not a precision resistor. For precision resistor, order 

PDX-RES2.

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.

General

Display:

 Wide viewing angle reverse polarity

LCD; PV: white, SV: green, MV: amber

PD510: PV and SV display

PD520: PV, SV, and MV display

PD530: PV, SV, and MV display

Display Height:

 inches (mm)

PV

SV

MV

PD510

0.60 (15.2)

0.29 (7.4)

N/A

PD520

0.81 (20.5)

0.50 (12.8)

0.37 (9.3)

PD530

1.14 (29.0)

0.59 (15.0)

0.43 (11.0)

PV Display Update Rate:

 4/second (250 ms)

Non-Volatile Memory:

 Settings stored for a minimum of 10 years.

EEPROM life: 1 million writes

Included Components:

 Controller with rubber gasket and mounting 

bracket, 250 Ω resistor (1%), and Quick Start Guide. 

Additional 250 Ω resistor (1%) provided for models with remote 

setpoint input option.

EEPROM Lock:

 Programmable lock or unlock write access to the 

EEPROM. When locked, setting changes stored in RAM (not saved 

on power down).

Power:

 100 - 240 VAC ±10%, 50 / 60 Hz, 8.5 VA max.

Insulation Resistance:

 20 MΩ minimum, 500 VDC

Dielectric Strength:

 3,000 VAC; 50/60 Hz for 1 minute across 

power terminals

Environmental:

 

Operating temperature range: -10 to 50°C  (14 to 122°F) 

Storage temperature range: -25 to 65°C (-40 to 185°F)

Relative humidity: 35 to 85% non-condensing

Front Panel:

 IP65

Depth Behind Panel: 

Case extends 2.5 in (63 mm) behind panel.

Required Fuse:

 UL Recognized, 250 VAC 0.5 A max, slow-blow 

fuse. Use fuses or circuit breakers compliant with IEC60947-1 or 

IEC60947-3

Connections:

 Fixed rear screw terminals and mini-USB

Mounting:

 1/16, 1/8, or 1/4 DIN panel cutout required: panel 

mounting bracket assemblies are provided.

Weight:

 PD510: 4.2 oz (120 g)

PD520: 7.1 oz (202 g)

PD530: 10.2 oz (290 g)

Warranty: 

1 year parts & labor. See Warranty Information and Terms & 

Conditions on www.predig.com for complete details.

Содержание PD510

Страница 1: ...and Heating Cooling Control Primary Control Output Options 4 20 mA SCR Voltage Pulse SSR or Relay Secondary Control Output Relay Standard on All Models Easily Switch Between Auto and Manual Control Modes Up to 2 Alarm Relays 4 20 mA Retransmit Outputs Remote Set Value 1 5 V Input Option 4 20 mA with External Resistor Digital Input Set Value Selection RS 485 Serial Communications Option Modbus RTU ...

Страница 2: ...ig com 2 TABLE OF CONTENTS OVERVIEW 3 EASY TO READ OPERATE 4 QUICK SETUP PROGRAMMING 4 PROCESS TEMPERATURE INPUTS 5 VERSATILE OPERATION 5 SUPERNOVA TCS SOFTWARE 7 NEMA 4 4X FIELD ENCLOSURES 8 DIMENSIONS 9 CONNECTIONS 10 SPECIFICATIONS 11 ORDERING INFORMATION 14 ...

Страница 3: ...to retransmit the process variable set value or output level This is especially useful for temperature inputs like thermocouples and RTDs Other options include a secondary 4 20 mA input to remotely control the set value and RS 485 for Modbus communication A mini USB port may be used for a direct PC connection to run the SuperNova software for monitoring programming and data logging This USB port i...

Страница 4: ...ped by category To access the group menus press and hold the Mode MD button for one second Navigate through the group menus using the UP or DOWN arrow buttons To enter a Group or change a parameter press SET Group Display Group Name General Description Set Value Group Select active Set Values and Set Value limits Input Group Configure input type and display scaling Output Group Configure control o...

Страница 5: ... two alarm relays two digital inputs serial communications and remote setpoint control make the SuperNova an excellent choice for any process or temperature control application requiring easy to change visible set points Main Control Secondary Outputs The main control output can be a 4 20 mA SCR voltage pulse SSR or relay output A secondary relay control output is standard which allow for one or t...

Страница 6: ...ons ability PDA7485 PDA8485 Analog Retransmit Output An optional 4 20 mA retransmitting output is available on all sizes of SuperNova Controllers This is especially useful when using a temperature input to provide a 4 20 mA signal to the control room or other equipment 4 20 mA Retransmitting Output Retransmit Based on PV SV or MV Auto Tuning PID A high accuracy auto tuning function calculates the ...

Страница 7: ...rd drive Data log files may be exported to HTML xls xlsx or pdf format as graphs or data tables Graphs may also be exported as bmp gif jpeg or png Data tables may also be exported as csv USB Powered USB port provides power to the controller for programming Apply normal power for general controller operations Remote Programming SuperNova TCS software allows all setup parameters to be programmed rem...

Страница 8: ...ontroller wiring Enclosures are available for 1 2 PD510 1 6 PD520 or 1 2 PD530 SuperNovas The enclosure is large enough to mount the PDA1024 01 DIN rail mounted 24 V transmitter supply Plastic Enclosures Internally Mounted PDA3400 Series Covers with screws The PDA3400 Series enclosures for the SuperNova fully cover the controller The controller is fully housed inside the enclosure behind a clear p...

Страница 9: ... 1 6 PD520 SuperNovas PDA2606 V with Six PD520s 1 8 DIN PDA2601 V with One PD520 1 8 DIN Steel Enclosures Externally Mounted PDA2700 Series Covers with Hinge Latch This is Precision Digital s painted steel line of enclosures for the SuperNova The controller mounts through a hinged cover with a latch allowing for easy access to controller wiring Enclosures are available for 1 6 PD520 SuperNovas PDA...

Страница 10: ...t s provided with the controller Insert controller into the panel cutout Install mounting bracket s and tighten the screws against the panel To achieve a proper seal tighten the mounting bracket screws evenly until controller is snug to the panel DO NOT OVER TIGHTEN as the rear of the panel may be damaged See Figure 1 and Figure 2 Figure 1 PD510 Mounting Bracket Installation Figure 2 PD520 PD530 M...

Страница 11: ...5 26 27 28 29 30 31 32 33 34 35 36 13 14 15 16 17 18 19 20 21 22 23 24 See Manual SUB1 SUB2 COM RLY RLY OUT1 OUT2 RTD mA V B A B TC RS485 A B SCR or SSR RLY 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 OUT2 RLY OUT1 RET REM RTD B A B TC mA V RS485 A B D I 1 COM D I 2 SUB1 SUB2 COM RLY RLY See Manual RLY PD510 R 1 16 DIN PD520 R 1 8 DIN PD530 R 1 4 DIN RET D I 1 COM D I 2 REM 1 2 3 4 5 6 7 8 9 10 1...

Страница 12: ...520 0 81 20 5 0 50 12 8 0 37 9 3 PD530 1 14 29 0 0 59 15 0 0 43 11 0 PV Display Update Rate 4 second 250 ms Non Volatile Memory Settings stored for a minimum of 10 years EEPROM life 1 million writes Included Components Controller with rubber gasket and mounting bracket 250 Ω resistor 1 and Quick Start Guide Additional 250 Ω resistor 1 provided for models with remote setpoint input option EEPROM Lo...

Страница 13: ...ce 600 Ω minimum Recommended minimum cycle time 1 sec Relay Output Rated resistive load switching capacity 5 A 250 VAC 5 A 30 VDC Max switching power 750 VA 90 W Max switching voltage 250 VAC 110 VDC Max switching current 5 A Mechanical life 20 million cycles at 180 CPM Recommended minimum cycle time 20 sec Alarm Relay Outputs Function Programmable for 13 different alarm types or off Number Two al...

Страница 14: ...ange 3 937 ft 1 2 km Baud Rate Programmable for 4800 9600 14400 19200 38400 57600 bps Start Bit 1 bit Data Bits Programmable for 7 or 8 bits Parity Programmable for none even or odd Stop Bit Programmable for 1 or 2 bits Protocol PC LINK STD PC LINK SUM MODBUS ASCII MODBUS RTU Response Time Actual response time processing time response time x 50 ms SuperNova TCS Software Availability Download direc...

Страница 15: ...elays 100 240 VAC PD520 S CTD Voltage Pulse SSR Relay Control Output 2 Alarm Relays RS 485 4 20 mA Retransmit 2 Digital Inputs 100 240 VAC PD520 S CTDR Voltage Pulse SSR Relay Control Output 2 Alarm Relays RS 485 4 20 mA Retransmit 2 Digital Inputs 4 20 mA SV Input 100 240 VAC PD520 R Relay On Off Relay Control Output 2 Alarm Relays 100 240 VAC PD520 R CTD Relay On Off Relay Control Output 2 Alarm...

Страница 16: ...2 Relay output for On Off control 2 SUB alarm relay outputs R Control OUT 1 Relay output for On Off or time proportional PID control Control OUT 2 Relay output for On Off control 2 SUB alarm relay outputs S Control OUT 1 Voltage pulse output for On Off or time proportional SSR PID control Control OUT 2 Relay output for On Off control 2 SUB alarm relay outputs Communication RS485 None C RS 485 comm...

Страница 17: ...1MA 1MA Signal Isolator with One 4 20 mA Input and One 4 20 mA Output PD659 1MA 2MA Signal Splitter with One 4 20 mA Input and Two 4 20 mA Outputs PD659 1V 1MA Signal Conditioner with One 0 10 VDC Input and One 4 20 mA Output PD659 1MA 1V Signal Conditioner with One 4 20 mA Input and One 0 10 VDC Output Your Local Distributor is Model Series Controllers Material Enclosures for PD510 1 16 DIN Contr...

Отзывы: