PD2-6300
Helios Large Display Pulse Input Rate/Totalizer Instruction Manual
25
Display
Parameter
Action/Setting Description
d-Inty
Display intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the
Relay
menu
Assign
Assignment
Assign relays to rate, total, or grand total
Asign1
Assign 1
Relay 1 assignment
rate
Rate
Assign relay to rate
totAL
Total
Assign relay to total
G total
Grand total
Assign relay to grand total
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Auto-manual
Set relay for automatic & manual reset any time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-cleared
Set relay for latching operation with manual reset only after alarm
condition has cleared
Altern
Alternate
Set relay for pump alternation control
Sanmpl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
Aout
Analog output
Enter the
Analog output
scaling menu
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value (e.g. 4.000 mA)
Dis 2
Display 2
Program display 2 value
Out 2
Output 2
Program output 2 value (e.g. 20.000 mA)