24
25
Ex / I.S. data:
Terminal 31...33
U
m
............................................................... : 250 V
Terminal 44 to 42, 41 (54 to 52, 51)
U
o
................................................................ : 28 VDC
I
o
.................................................................. : 91 mADC
P
o
................................................................ : 0.65 W
L
o
................................................................. : 3.0 mH
C
o
................................................................ : 80 nF
Terminal 41 to 42 (51 to 52)
U
o
................................................................ : 10 VDC
I
o
.................................................................. : 2 mADC
P
o
................................................................ : 5 mW
L
o
................................................................. : 1 H
C
o
................................................................ : 3 µF
GOST R approval:
VNIIM & VNIIFTRI, Cert. no. ........................ See www.prelectronics.com
Observed authority requirements:
Standard:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
PELV/SELV ................................................... IEC 364-4-41
and EN 60742
ATEX 94/9/EC .............................................. EN 50014, EN 50020 and
EN 50281-1-1
UL ................................................................ UL 913, UL 508
Of span =
of the presently selected range
Auxiliary supply:
2-wire supply (pin 44...42 & 54...52) ........... 25...17 VDC / 0...20 mA
Max. wire size .............................................. 1 x 2.5 mm
2
stranded wire
Screw terminal torsion ................................ 0.5 Nm
Relative humidity ......................................... < 95% RH (non-cond.)
Dimensions (HxWxD) ................................... 109 x 23.5 x 130 mm
DIN rail type ................................................. DIN 46277
Protection degree ........................................ IP20
Weight ......................................................... 246 g
Current input:
Measurement range .................................... 4...20 mA
Min. measurement range (span).................. 16 mA
Input resistance:
Supplied unit ............................................... Nom. 10
Ω
Non-supplied unit ........................................ Rshunt =
∞
, Vdrop < 4 V
Current output and 2-wire 4...20 mA output:
Signal range (span) ...................................... 4...20 mA
Min. signal range (span) .............................. 16 mA
Load (max.) .................................................. 20 mA / 600
Ω
/ 12 VDC
Load stability ...............................................
≤
0.01% of span / 100
Ω
Current limit .................................................
≤
28 mA
Ripple on HART
®
communication ............... < 3 m
VRMS
Max. external 2-wire supply ........................ 29 VDC
Effect of external 2-wire supply
voltage change ............................................ < 0.005% of span / V
EEx / I.S. approval - 5106B:
DEMKO 00ATEX127483 ..............................
II (1) GD
[EEx ia] IIC
Applicable for .............................................. Zone 0, 1, 2, 20, 21 or 22
UL ................................................................ IS, Cl. I, Div. 1, Group A, B, C, D
IS, Cl. I, zone 0 and 1, Group IIC
IS, Cl. II, Div. 1, Group E, F,G
UL control drawing no. ........................ 5106QU01
EMC immunity influence ..................................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst ....................... < ±1% of span