533XQC03.DOC
2006-01-04 Rev. AB
1/2
CSA Installation Drawing 533XQC03.
5331D, 5333D and 5335D transmitters are intrinsically safe in Zone 0 Group IIC
or Class I, Division1, Group A,B,C,D when installed according to Installation
Drawing.
1. Connections with separate power supply and receiver.
Output:
Standard 4 – 20 mA loop
Non
hazardous
Location
max. 250 V
T4:-40 to + 85 deg. Celcius
T6:-40 to + 60 deg. Celcius
Separate Power
Supply
Receiving
Instrument
Hazardous
Locations /
Sécurité
Intrinséque
+
-
-
+
-
Ambient temperature limits
Intrinsically safe
Barrier Parameters.
Uo(Voc) =< 30 V
Io(Isc) =< 120 mA
Po =< 0.84 W
CSA approved
Barrier
Terminal: 1-2
Ui(Vmax) = 30 V
Ii(Imax) = 120 mA
Pi
= 0.84 W
Ci
= 1 nF
Li
= 10 uH
Co(Ca)>Sum(Ci+Ccable)
Lo(La)>Sum(Li+Lcable)
+
SENSOR
1
2
3
4
5
6
5335D
Terminal: 3,4,5,6
Only passive, or non-energy
storing devices such as
RTD's and Thermocouples
may be connected.
Terminal: 3,4,5,6
Uo(Voc) = 9.6 V
Io(Isc)
= 28 mA
Po
= 67.2 mW
Co(Ca) = 3.5 uF
Lo(La) = 35 mH
5331D or
5333D
5331D or
5333D or
5335D
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation
codes stipulated in the Canadian Electrical Code (CEC).
533XQC03.DOC
2006-01-04 Rev. AB
2/2
2. Connection with power supply and barrier built into receiver.
Output:
Standard 4 - 20 mA loop
Non-
hazardous
location
max. 250 V
Hazardous
Locations /
Sécurité
Intrinséque
Transmitter
Power Supply
built into
CSA approved
Receiving
Instrument
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Intrinsically safe
Barrier Parameters.
Uo(Voc) =< 30 V
Io(Isc)
=< 120 mA
Po(Pmax) =< 0.84 W
Ca>Sum(Ci)+Ccable
La>Sum(Li)+Lcable
SENSOR
1
2
3
4
5
6
+
-
5331D or
5333D or
5335D
Terminal: 3,4,5,6
Uo(Voc) = 9.6 V
Io(Isc) = 28 mA
Po
= 67.2 mW
Co(Ca) = 3.5 uF
Lo(La)
= 35 mH
Terminal: 3,4,5,6
Only passive, or non-energy
storing devices such as
RTD's and Thermocouples
may be connected.
Terminal: 1-2
Ui(Vmax) = 30 V
Ii(Imax) = 120 mA
Pi
= 0.84 W
Ci
= 1 nF
Li
= 10 uH
5331D or
5333D
5335D
Warning:
Substitution of components may impair intrinsic safety.
The Transmitters must be installed in a suitable enclosure to meet installation
codes stipulated in the Canadian Electrical Code (CEC).