5715V102-UK 19
REL1
SET
--> ENTER RELAY 1 SETUP
SKIP --> SKIP RELAY 1 SETUP
OFF
--> RELAY 1 DISABLED
SETP
xxxx
--> RELAY SETPOINT
AcT1
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HyS1
xxxx
--> RELAY HYSTERESIS
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
oN.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
oF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
RELx (x = 2...4)
SET
--> ENTER RELAY 2 SETUP
SKIP --> SKIP RELAY 2 SETUP
OFF
--> RELAY 2 DISABLED
SETP
xxxx
--> RELAY SETPOINT
AcTx (x = 2...4)
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HySx (x = 2...4)
xxxx
--> RELAY HYSTERESIS
ERRx (x = 2...4)
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
oN.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
oF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
A.oUT
0-20
--> OUTPUT RANGE IN mA
4-20
--> OUTPUT RANGE IN mA
20-0
--> OUTPUT RANGE IN mA
20-4
--> OUTPUT RANGE IN mA
o.Lo
xxxx
--> DISPLAY VALUE FOR OUTPUT LOW
o.HI
xxxx
--> DISPLAY VALUE FOR OUTPUT HIGH
o.ERR
23 mA --> NAMUR NE43 UPSCALE AT ERROR
3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR
0mA
--> DOWNSCALE AT ERROR
NONE --> UNDEFINED OUTPUT AT ERROR
RESP
xxx.x --> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
E.PAS
NO
--> ENABLE PASSWORD PROTECTION
YES
N.PAS
xxxx
--> SELECT NEW PASSWORD
ADV mENU:
LANG --> ENTER LANGUAGE SETUP
DISP --> ENTER DISPLAY SETUP
CAL
--> PERFORM PROCESS CALIBRATION
HLP.T
DE
--> DE - WAEHLE DEUTSCHEN HILFETEXT
DK
--> DK - VAELG DANSK HJAELPETEKST
ES
--> ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR
--> FR - SELECTION TEXTE D’AIDE
EN FRANCAIS
IT
--> IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE
--> SE - VALJ SVENSK HJALPTEXT
UK
--> UK - SELECT ENGLISH HELPTEXT
CZ
--> CZ - VYBER CESKOU NAPOVEDU
LIGH
xxxx
--> ADJUST DISPLAY LIGHT INTENSITY
cA.Lo
YES
--> CALIBRATE INPUT LOW TO PROCESS
VALUE?
NO
cA.HI
YES
--> CALIBRATE INPUT HIGH TO PROCESS
VALUE?
NO
VAL.L
xxxx
--> SET VALUE FOR LOW CALIBRATION
POINT
VAL.H
xxxx
--> SET VALUE FOR HIGH CALIBRATION
POINT
USE.c
YES
--> USE PROCESS CALIBRATED VALUES?
NO