2 4222MCM101
4222 Configuration Parameter List
Category
Parameter
Name
No. Register
Address
Register
Size
Read/
Write
Type
Description
Values
GENERAL
DEVICE NUMBER
0
0
1
RO
UNSIGNED
INTEGER
Defines the
actual device type
4222 = 16930 (0x4222)
GENERAL
DEVICE VERSION
1
1
1
RO
UNSIGNED
INTEGER
Product version
0
GENERAL
PASSWORD
2
2
1
R/W
UNSIGNED
INTEGER
Password
for entering
configuration menu
Range: 0...9999
INPUT
INPUT TYPE
3
3
1
R/W
UNSIGNED
INTEGER
Selected input type
(Voltage, Current,
Resistance,
Potentiometer,
Temperature)
TEMP = 0
POTM = 1
LINR = 2
CURR = 3
VOLT = 4
INPUT
INPUT VOLTAGE
RANGE
4
4
1
R/W
UNSIGNED
INTEGER
Fixed input range for
voltage
measurements
0...1 V
=
0
0.2...1 V
=
1
0...2.5 V
=
2
0.5...2.5 V =
3
0...5 V
=
4
1...5 V
=
5
0...10 V
=
6
2...10 V
=
7
INPUT
INPUT CURRENT
RANGE
5
5
1
R/W
UNSIGNED
INTEGER
Fixed input range for
current
measurements
0...20 mA =
0
4...20 mA =
1
INPUT
CONNECTION
TYPE
6
6
1
R/W
UNSIGNED
INTEGER
Sensor
connection type
for RTD / resistance
measurements
2-wire
=
0
3-wire
=
1
4-wire
=
2
INPUT
LIN RES LOW
7
7
1
R/W
UNSIGNED
INTEGER
Input range low for
Linear resistance meas-
urements
Range: 0...9998
INPUT
LIN RES HIGH
8
8
1
R/W
UNSIGNED
INTEGER
Input range high for
Linear resistance meas-
urements.
Range: 1...9999
INPUT
TEMP UNIT
9
9
1
R/W
UNSIGNED
INTEGER
Temperature units
°C
=
0
°F
=
1
INPUT
TEMP SENSOR
TYPE
10
10
1
R/W
UNSIGNED
INTEGER
Temperature
sensor type
TC
=
0
Ni
=
1
Pt
=
2
INPUT
PT TYPE
11
11
1
R/W
UNSIGNED
INTEGER
Pt value
(Pt10, Pt20, Pt50...)
Pt10
=
0
Pt20
=
1
Pt50
=
2
Pt100
=
3
Pt200
=
4
Pt250
=
5
Pt300
=
6
Pt400
=
7
Pt500
=
8
Pt1000
=
9
INPUT
NI TYPE
12
12
1
R/W
UNSIGNED
INTEGER
Ni value
(Ni50, Ni100...)
Ni50
=
0
Ni100
=
1
Ni120
=
2
Ni1000
=
3
INPUT
TC TYPE
13
13
1
R/W
UNSIGNED
INTEGER
Thermocouple type
(TCB, TCK...)
TC type B =
0
TC type E =
1
TC type J =
2
TC type K =
3
TC type L =
4
TC type N =
5
TC type R =
6
TC type S =
7
TC type T =
8
TC type U =
9
TC type W3 =
10
TC type W5 =
11
TC type Lr = 12
DISPLAy
DISPLAY UNIT
14
14
1
R/W
UNSIGNED
INTEGER
Units shown as display
units for non-tempera-
ture input types
acc. to table 1
DISPLAy
DECIMAL POINT
15
15
1
R/W
UNSIGNED
INTEGER
Decimal point place for
display reading of non-
temperature input types
XXXX
=
0
X.XXX
=
1
XX.XX
=
2
XXX.X
=
3
DISPLAy
DISPLAY LOW
16
16
1
R/W
INTEGER
Low display range
for display reading of
non-temperature input
types.
Range: -1999...9999
DISPLAy
DISPLAY HIGH
17
17
1
R/W
INTEGER
High display range for
display reading of non-
temperature input types
Range: -1999...9999
OUTPUT
OUTPUT TYPE
18
18
1
R/W
UNSIGNED
INTEGER
Output type:
Programmable pulse is
available for:
Frequency < 500 Hz
Pulses < 30,000 p/m
< 1,800,000 p/hour
< 43,200,000 p/day
DC 50%
=
0
Prog Pulse
=
1
OUTPUT
OUTPUT UNIT
19
19
1
R/W
UNSIGNED
INTEGER
Output unit
Hz
=
0
p/min
=
1
p/hour
=
2
p/day
=
3