2 4222MCM101

4222 Configuration Parameter List

Category

Parameter 

Name

No. Register 

Address

Register 

Size

Read/

Write

Type

Description

Values

GENERAL

DEVICE NUMBER

0

0

1

RO

UNSIGNED 

INTEGER

Defines the 

actual device type

4222 = 16930 (0x4222)

GENERAL

DEVICE VERSION

1

1

1

RO

UNSIGNED 

INTEGER

Product version

0

GENERAL

PASSWORD

2

2

1

R/W

UNSIGNED 

INTEGER

Password 

for entering  

configuration menu

Range: 0...9999

INPUT

INPUT TYPE

3

3

1

R/W

UNSIGNED 

INTEGER

Selected input type 

(Voltage, Current, 

Resistance, 

Potentiometer, 

Temperature)

TEMP = 0

POTM =  1

LINR  = 2

CURR = 3

VOLT  = 4

INPUT

INPUT VOLTAGE 

RANGE

4

4

1

R/W

UNSIGNED 

INTEGER

Fixed input range for 

voltage  

measurements

0...1 V 

0

0.2...1 V 

1

0...2.5 V 

2

0.5...2.5 V  = 

3

0...5 V 

4

1...5 V 

5

0...10 V 

6

2...10 V 

7

INPUT

INPUT CURRENT 

RANGE

5

5

1

R/W

UNSIGNED 

INTEGER

Fixed input range for 

current  

measurements

0...20 mA   =  

0

4...20 mA   =  

1

INPUT

CONNECTION 

TYPE

6

6

1

R/W

UNSIGNED 

INTEGER

Sensor 

connection type 

for RTD / resistance 

measurements

2-wire  

3-wire  

=  

4-wire  

=  

2

INPUT

LIN RES LOW

7

7

1

R/W

UNSIGNED 

INTEGER

Input range low for 

Linear resistance meas-

urements

Range: 0...9998

INPUT

LIN RES HIGH

8

8

1

R/W

UNSIGNED 

INTEGER

Input range high for 

Linear resistance meas-

urements.

Range: 1...9999

INPUT

TEMP UNIT

9

9

1

R/W

UNSIGNED 

INTEGER

Temperature units 

°C  

=  

°F  

=  

1

INPUT

TEMP SENSOR 

TYPE

10

10

1

R/W

UNSIGNED 

INTEGER

Temperature 

sensor type

TC  

=  

Ni  

=  

Pt  

=  

2

INPUT

PT TYPE

11

11

1

R/W

UNSIGNED 

INTEGER

Pt value 

(Pt10, Pt20, Pt50...)

Pt10  

=  

0

Pt20  

=  

1

Pt50  

=  

2

Pt100  

=  

3

Pt200  

=  

4

Pt250  

=  

5

Pt300  

=  

6

Pt400  

=  

7

Pt500  

=  

8

Pt1000  

=  

9

INPUT

NI TYPE

12

12

1

R/W

UNSIGNED 

INTEGER

Ni value 

(Ni50, Ni100...)

Ni50  

=  

Ni100  

=  

Ni120  

=  

Ni1000  

=  

3

INPUT

TC TYPE

13

13

1

R/W

UNSIGNED 

INTEGER

Thermocouple type 

(TCB, TCK...)

TC type B   =  

0

TC type E   =  

1

TC type J   =  

2

TC type K   =  

3

TC type L   =  

4

TC type N   =  

5

TC type R   =  

6

TC type S   =  

7

TC type T   =  

8

TC type U   =  

9

TC type W3 =  

10

TC type W5 =  

11

TC type Lr =  12

DISPLAy

DISPLAY UNIT

14

14

1

R/W

UNSIGNED 

INTEGER

Units shown as display 

units for non-tempera-

ture input types

acc. to table 1

DISPLAy

DECIMAL POINT

15

15

1

R/W

UNSIGNED 

INTEGER

Decimal point place for 

display reading of non-

temperature input types

XXXX  

=  

0

X.XXX  

=  

1

XX.XX  

=  

2

XXX.X  

=  

3

DISPLAy

DISPLAY LOW

16

16

1

R/W

INTEGER

Low display range 

for display reading of 

non-temperature input 

types.

Range: -1999...9999

DISPLAy

DISPLAY HIGH

17

17

1

R/W

INTEGER

High display range for 

display reading of non-

temperature input types

Range: -1999...9999

OUTPUT

OUTPUT TYPE

18

18

1

R/W

UNSIGNED 

INTEGER

Output type:

 

Programmable pulse is 

available for:

Frequency < 500 Hz

Pulses < 30,000 p/m

< 1,800,000 p/hour

< 43,200,000 p/day

DC 50% 

=  

0

Prog Pulse 

=  

1

OUTPUT

OUTPUT UNIT

19

19

1

R/W

UNSIGNED 

INTEGER

Output unit

Hz 

=  

0

p/min 

=  

1

p/hour 

=  

2

p/day 

=  

3

Содержание 4511

Страница 1: ...4511 MODBUS RTU Configuration Manual 4 2 2 2 Universal I f converter N o 4 2 2 2 M C M 1 0 1 1 4 4 5 F o r 4 5 1 1 d e v i c e s f r o m s e r n o 1 4 1 5 9 0 0 0 1 ...

Страница 2: ...gment line termination 1 4222 Configuration Parameter List 2 General 2 Input 2 Display 2 Output 2 Table 1 Display units 4 4222 Input Types and Ranges 4 4222 Process Parameter List 5 4511 Modbus Configuration Parameter List 6 4511 Additional Parameter List 6 4511 Modbus Status Parameter List 6 4511 Modbus Front Programming Parameter Menu 7 ...

Страница 3: ...odes Command Function code Read Holding Registers 03 Read Input Registers 04 Write Single Register 06 Diagnostics 08 Write Multiple Registers 16 The Function Code defines the command that the slave device is to execute such as read data accept data report status Some function codes have sub function codes The Data defines addresses in the device s memory map for read functions contains data values...

Страница 4: ...R W UNSIGNED INTEGER Temperature units C 0 F 1 Input TEMP SENSOR TYPE 10 10 1 R W UNSIGNED INTEGER Temperature sensor type TC 0 Ni 1 Pt 2 Input PT TYPE 11 11 1 R W UNSIGNED INTEGER Pt value Pt10 Pt20 Pt50 Pt10 0 Pt20 1 Pt50 2 Pt100 3 Pt200 4 Pt250 5 Pt300 6 Pt400 7 Pt500 8 Pt1000 9 Input NI TYPE 12 12 1 R W UNSIGNED INTEGER Ni value Ni50 Ni100 Ni50 0 Ni100 1 Ni120 2 Ni1000 3 Input TC TYPE 13 13 1 ...

Страница 5: ... types value is 1 10 Range equals the measurement range for the selected sensor type and must be higher than OUTPUT LOW Display DISPLAY CONTRAST 29 35 1 R W UNSIGNED INTEGER Contrast in the LCD display Range 0 9 Display DISPLAY BACKLIGHT 30 36 1 R W UNSIGNED INTEGER Backlight intensity in LCD Range 0 9 Display TAG TEXT 31 37 3 R W ASCII CHAR Tag of the device 6 characters Range ASCII values from 3...

Страница 6: ...584 1 DIN 43710 IEC 60584 1 IEC 60584 1 IEC 60584 1 IEC 60584 1 DIN 43710 ASTM E988 90 ASTM E988 90 GOST 3044 84 4222 Input Types and Ranges 0 C 10 mils 20 in s 30 kHz 40 MPa 50 GW 60 mV 70 gal h 1 F 11 yd 21 ips 31 Hz 41 kPa 51 MW 61 W 71 t h 2 K 12 m3 22 ft s 32 p min 42 hPa 52 kW 62 S 72 mol 3 13 L 23 in min 33 p h 43 bar 53 hp 63 µS 73 pH 4 m 14 s 24 ft min 34 p day 44 mbar 54 A 64 m3 min 74 b...

Страница 7: ...Range for non temperature input types DISPLAY LOW DISPLAY HIGH Range for temperature input types equals the measurement range for the selected sensor type PRIMARY VALUE 6 1007 2 R W FLOAT The measured value in 1 10 of C F for temperature Input types or the scaled display value for non temperature input types Range for non temperature input types DISPLAY LOW DISPLAY HIGH Range for temperature input...

Страница 8: ...DDRESS 6 3005 1 R W INTEGER Configures the Modbus address of the 4511 Address 0 is broadcast address Range 1 247 RESPONSE DELAY 7 3006 1 R W INTEGER Configures minimum delay for Modbus response in ms Range 0 1000 4511 Modbus Status Parameter List Parameter Name No Register Address Register Size Read Write Type Description Values AUTOBAUD STATUS 1 4000 1 RO INTEGER Actual state of automatic baudrat...

Страница 9: ...e 4511 The actual placement is defined for each particular device Scrolling HELP TEXTS 1 Set correct password 2 Enter advanced setup menu 3 Perform memory operations Enter display setup Perform process calibration Enter simulation setup Enter password setup Enter language setup Enter rail setup System 9000 Enter Modbus setup 4 Check automatic baudrate detection status Enable Modbus communication D...

Отзывы: