1 2 3 4 5 6 7 8 9 10
Filter ON
Bandwidth
10 Hz
Filter OFF
Bandwidth
> 100 Hz
Input
Current
-10...+10 mA
Input
Current
-20...+20 mA
Input
Voltage
-5...+5 V
Input
Voltage
-10...+10 V
Output
Current
0...20 mA
Output
Current
4...20 mA
Output
Voltage
0...10 V
Output
Voltage
2...10 V
Output
Voltage
0...5 V
Output
Voltage
1...5 V
12
3117V100-UK
Approvals:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 61010-1
Safe Isolation ............................................... EN 61140
GOST R
marine:
Det Norske Veritas, Ships & Offshore ......... Stand. f. Certific. No. 2.4
Germanischer Lloyd .................................... VI-7-2
Ex:
ATEX 94/9/EC .............................................. KEMA 10ATEX0147 X
IECEx ........................................................... KEM 10.0068 X
c FM us ....................................................... 3041043-C
DIp-switch configuration
DIP-switch positions are only read at power up
Front LED indication (green)
LED
condition
output
Action required
OFF
No supply/device error
De-energized
Connect supply/replace device
1 flash 0.5 s ON and OFF
Power-up or Restart
De-energized
-
Flashing 13 Hz / 15 ms ON
Device OK
Energized
-
Flashing 1 Hz / 15 ms ON
Incorrect DIP-sw setting
De-energized
Correct setting and repower
Flashing 13 Hz / 0.5 s ON
Supply or hardware error
De-energized
Check supply/replace device