  3225V100-UK 5

Safety instructions

Definitions 

Hazardous voltages

 have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC. 

Technicians

 are qualified persons educated or trained to mount, operate, and also trouble-shoot technically correct and in 

accordance with safety regulations. 

Operators

 are personnel familiar with the contents of this manual and capable of safe operation of the device.

Receipt and unpacking

Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing 
should always follow the device until this has been permanently mounted.

Environment

Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary, 
heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. 
The device must be installed in pollution degree 2 or better.  
The device is designed to be safe at least under an altitude up to 2000 m.
The device is designed for indoor use.

Mounting

Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to 
follow these should connect the device. Should there be any doubt as to the correct handling of the device, please contact 
your local distributor or, alternatively,

PR electronics A/S

www.prelectronics.com

Mounting and connection of the device should comply with national legislation for mounting of electric materials, e.g. wire 
cross section, protective fuse, and location. 

Descriptions of input / output and supply connections are shown in the block diagram and side label.

The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced 
insulation. A power switch should be easily accessible and close to the device. The power switch shall be marked as the 
disconnecting unit for the device.

SYSTEM 3000 must be mounted on a DIN rail according to EN 60715.

Year of manufacture can be taken from the first two digits in the serial number.

Calibration and adjustment

During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the 
specifications of this manual. The technician must use tools and instruments that are safe to use.

Normal operation

Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of 
personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible.

Cleaning

When disconnected, the device may be cleaned with a cloth moistened with distilled water.

Liability

To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR 
electronics A/S that would otherwise exist according to the concluded sales agreement.

Содержание 3225A

Страница 1: ...DE SMARTER Zone 2 ZONE 2 P E N D I N G Product manual 3225 Universal frequency converter TEMPERATURE I S INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No 3225V100 UK From seria...

Страница 2: ...sive easy to use future ready communication interfaces that can access your PR installed base of products All the interfaces are detachable have a built in display for readout of process values and di...

Страница 3: ...characteristics 12 Programming 17 DIP switch configuration 17 PR 4590 ConfigMate programming 19 Configurable input error indication and input limits 20 Low cut off function 22 Square root function 22...

Страница 4: ...ld only be carried out on a disconnected device and under ESD safe conditions General mounting connection and disconnection of wires Troubleshooting the device Repair of the device and replacement of...

Страница 5: ...tronics A S www prelectronics com Mounting and connection of the device should comply with national legislation for mounting of electric materials e g wire cross section protective fuse and location D...

Страница 6: ...zardous voltages Detach the device from the rail by moving the bottom lock down System 3000 devices can be mounted on DIN rail or power rail where applicable When installing system 3000 devices with p...

Страница 7: ...by a module stop PR part number 9404 Power supply units can be mounted on the power rail according to customer requirements Marking The front cover of the 3225 has been designed with an area for affi...

Страница 8: ...ely you can connect 24 VDC to any 3000 device with power rail connector which will then energize other units on the rail Power rail solution 3 The PR 9410 power control unit can energize and power 96...

Страница 9: ...multaneous sensor error detection PATENTED All terminals are over voltage protected polarity protected and short circuit protected Technical highlights Accuracy 0 06 span Temperature coefficient 0 006...

Страница 10: ...t 3225B Power rail connections Only type 3225A with power rail option 3225A Contact NPN Special trig current voltage TTL S0 NAMUR PNP NPN Tacho Supply Supply Supply Supply Rail supply Rail supply No c...

Страница 11: ...3225V100 UK 11 Block diagram 3225 4 3 2 1 5 8 7 6 f in D A 3225A 3225B R CPU VReg 5 17 V Supply Supply Green Yellow VBuf Yellow Freq detector CPU Red...

Страница 12: ...h serial number 211394001 Accessories for power rail devices 3405 Power rail connector unit 9400 Power rail 7 5 or 15 mm high 9410 Power control unit 9421 Power supply Technical characteristics Enviro...

Страница 13: ...perature coefficient Frequency input 0 100 kHz 0 01 of input frequency 0 0005 C Basic values Input type Range s Basic accuracy Temperature coefficient Frequency input 0 100 kHz 0 0002 Hz 0 0005 C Outp...

Страница 14: ...acc to DIN 43864 Trig level LOW 2 2 mA Trig level HIGH 9 0 mA Input impedance 758 220 pF Sensor supply 17 V 23 mA NAMUR input NAMUR according to EN 60947 5 6 Trig level LOW 1 2 mA Trig level HIGH 2 1...

Страница 15: ...time programmable 0 60 s Sensor error detection 0 3 5 23 mA none Input limiters error indication levels See tables on page 21 Current limit 28 mA Voltage output Signal range 11 5 VDC Programmable stan...

Страница 16: ...01 1 10 100 10 1000 Observed authority requirements EMC 2014 30 EU UK SI 2016 1091 LVD 2014 35 EU UK SI 2016 1101 RoHS 2011 65 EU UK SI 2012 3032 ATEX 2014 34 EU UK SI 2016 1107 Approvals c UL us UL...

Страница 17: ...ay and verify parameter values and device status For DIP switch programming the non DIP switch programmable parameters are set at factory default values Calculating DIP switch settings for Input high...

Страница 18: ...18 3225V100 UK DIP switch settings 3225A DIP switch settings 3225B For easy DIP switch programming our DIP switch configurator can be found at www prelectronics com dip switch configurator...

Страница 19: ...3225 and inserting the jack into the plug A reference for the complete menu structure and programming options can be found in the section Routing diagram on page 28 For further information on how to n...

Страница 20: ...NE43 for a 4 20 mA output span For all other output spans equivalent output error indications are used see tables on page 21 When input limit is enabled and error state NONE is selected the input erro...

Страница 21: ...error indication 0 20 mA 0 mA 23 mA 0 mA 20 5 mA 23 mA 0 mA 0 mA No error indication Output limits and error indications voltage output Input limit disabled NAMUR sensor error detection input limit e...

Страница 22: ...te Time Time 8 ms 8 ms 8 ms 8 ms 8 ms 8 ms 1111 s or 2 s Input low cut off Default configured for 1111 s 0 0009 Hz or 2 s 0 5 Hz with L COF enabled Square root function A Square root function can be a...

Страница 23: ...ship either changes to a linear relationship or the output is truncated to zero The two principles are illustrated below Linear cut off in_min 0 0 Output range Input range 0 144 1 15 0 288 0 719 0 431...

Страница 24: ...25B 3 different settings of relay function can be selected Setpoint The device works as a single limit switch Window The relay has a window that is defined by a low and high setpoint On both sides of...

Страница 25: ...esis 10 Setpoint 50 Relay action Increasing Relay action Decreasing 1 2 Normal function Relay configured for N O Inverse function Relay configured for N C 1 2 1 2 Relay function Active Inside Window A...

Страница 26: ...ay OFF delay Relay latched Relay latched Closed Open Relay contact N O Release not possible still inside window Release not possible inside hysteresis Release not possible OFF delay still active Relea...

Страница 27: ...l value is entered via the PR 4500 communication interface If you accept to use the calibration the device will work according to this new adjustment If you later reject this menu point or choose anot...

Страница 28: ...M 9 64 40 0 100 0 0 0 9 10 OK NO YES OK Default State 66 EN PASS NO YES NO PASS 67 NEW PAS 0000 9999 0000 OK NO YES OK 69 LANGUA UK ES LANG UK OK 71 I FUNC NONE SQRT L COF IFUN 76 SQRT LO 0 000 0 000...

Страница 29: ...1 64 40 0 100 0 0 0 11 12 OK NO YES OK Default State 66 EN PASS NO YES NO PASS 67 NEW PAS 0000 9999 0000 OK NO YES OK 69 LANGUA UK ES LANG UK OK 71 I FUNC NONE SQRT L COF IFUN 76 SQRT LO 0 000 0 000 1...

Страница 30: ...in of input range Set up relay in display units 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 19 20 21 30 Select WINDOW function relay is controlled by 2 setpoints Select SETPOINT function relay is contr...

Страница 31: ...ity Select language Enable Relay Latch function Select no input function Select 0 5 Hz low cut off on input No effect on period time input Select Square Root Input Function Relay setpoint press 3 to s...

Страница 32: ...status is easy from either the front LEDs Status indicators front LEDs Indicator Indicator pattern Condition Power 13 Hz 250 ms Normal operation 1 Hz 2 ms Device OK Sensor or Input limit error Solid I...

Страница 33: ...fied personnel who are familiar with the national and international laws directives and standards that apply to this area The devices shall be installed in a suitable enclosure providing a degree of p...

Страница 34: ...34 3225V100 UK Document history The following list provides notes concerning revisions of this document Rev ID Date Notes 100 2204 Initial release of the product...

Страница 35: ...ntation We are headquartered in Denmark and have offices and authorized partners the world over We are a local business with a global reach This means that we are always nearby and know your local mar...

Страница 36: ...ndards for products communicating monitoring and connecting our customers process measurement points to their process control systems Our innovative patented technologies are derived from our extensiv...

Отзывы: