Chapter 5 Function parameter
172
inductance
(inverter power <= 55kW)
0.001mH to 65.535mH
(inverter power> 55kW)
b0.14
Synchronous counter
EMF coefficient
0.1V to 6553.5V
-
★
b0.15 to
b0.26
Reserve
b0.27
Motor parameter auto
tunning
No operation
0
0
★
Asynchronous
motor parameters
still auto tunning
1
Asynchronous
motor parameters
comprehensive
auto tunning
2
Synchronous
motor parameters
self-learning with
load
11
Synchronous
motor parameters
self-learning
without load
12
If the motor is able to disengage the load, in order to obtain a better operating
performance, you can choose comprehensive auto tunning; otherwise, you can only select
parameters still auto tunning. Firstly set the parameter according to load condition, and then
press RUN key, the inverter will perform parameters auto tunning. Parameters auto tunning
can be performed only under keyboard operation mode, is not suitable for terminal operation
mode and communication operation mode.
0: no operation, which prohibits parameters auto tunning.
1: asynchronous motor parameters still auto tunning
Motor type and motor nameplate parameters b0.00 to b0.05 must be set correctly before
performing asynchronous motor parameters still auto tunning. The inverter can obtain b0.06
to b0.08 three parameters before performing asynchronous motor parameters still auto
tunning.
2: asynchronous motor parameters comprehensive auto tunning
During asynchronous motor parameters comprehensive auto tunning, the inverter firstly
performs parameters still auto tunning, and then accelerates up to 80% of the rated motor
frequency according to the acceleration time F0.13, after a period of time, and then
decelerates till stop according to the deceleration time F0.14 to end auto tunning.
Before preforming asynchronous motor parameters comprehensive auto tunning, not
only motor type and motor nameplate parameters b0.00 to b0.05 must be set properly, but
also encoder type and encoder pulses b0.29, b0.28.
For asynchronous motor parameters comprehensive auto tunning, the inverter can obtain
b0.06 to b0.10 five motor parameters, as well as the AB phase sequence b0.31 of encoder,
vector control current loop PI parameters F5.12 to F5.15.
11:
Synchronous motor parameters self-learning with load