Chapter 5 Function parameter
137
When the inverter's output frequency randomly reaches the range of the detected
value(positive or negative), the multi-function DO will output ON signal.
PI9000 provides two groups of parameter to set frequency value and frequency
detection range. The above figure is the schematic diagram of the function.
F7.32
Zero current detection level
0.0% to 300.0% (rated
motor current)
5.0%
☆
F7.33
Zero current detection delay
time
0.01s to 360.00s
0.10s
☆
Zero current
detection level
F7.32
Time t
Output
F7.33
Zero current detection delay time
Time t
Zero current
detection signal
ON
When the inverter's output current is less than or equal to zero current detection level
and lasts for longer than the delay time of zero-current detection, the inverter's multifunction
DO will output ON signal. The figure is the schematic diagram of zero current detection.
F7.34
Overrun value of output
current
0.0% (not detected)
0.1% to 300.0% (rated
motor current)
200.0%
☆
F7.35
Output Current overrun
detection delay time
0.01s to 360.00s
0.00s
☆
任意到达频率检测示意图
运行频率
时间
t
任意到达频率
任意到达频率
检测信号
DO
或
继电器
ON
ON
OFF
OFF
OFF
频率检出宽度
频率检出宽度
running
frequency
Random arrivals frequency
Random arrivals frequency
detection signal DO or
relay
Frequency detection range
Schematic diagram of random arrivals frequency detection
Time