selection

1: Compensation mode 1

2: Compensation mode 2

Fb.04 Current detection compensation 0

100

5

Fb.05 Vector optimization without PG

mode selection

0: No optimization

1: Optimization mode 1

2: Optimization mode 2

1

Fb.06 Upper limiting frequency for

DPWM switching

0.00

15.00Hz

12.00Hz

Fb.07 PWM modulation manner

0:Asynchronous;1:Synchronous

0

Fb.08 Random PWM depth

0: Invalid

1~10: PWM carrier frequency random depth

0

E0 group Wobbulate, fixed-length and counting

Code

Parameter name

Setting range

Factory

setting

Change

E0.00 Solar operation mode selection

0: Control mode invalid;

1:CVT Mode;

2: MPPT Mode

2

0: PV invalid Photovoltaic effect does not work; when normal operation model, need to set E0.00=0.

1: CVT mode Bus voltage is constant as a given value, F0.03 is set to 8, photovoltaic mode, bus

voltageis given as E0.01, feedback the current bus voltage.

2: MPPT mode Bus voltage is given as the maximum power search result, F0.03 is set to 8,

photovoltaicmode. When starting but before the searching, the bus voltage is given as E0.01, atintervals after

the search, the search result is as given value.

E0.01 Solar voltage setting

Solar voltage setting

Confirmed

model type

When set E0.00 to 1, this voltage is CVT mode bus voltage set value;

When set E0.00 to 2, the voltage is the bus voltage given value when MPPT mode be started,and also

the initial value when search voltage.Appropriate adjustments according to the site conditions.

Note: the set value should be lower than the bus voltage value, if the value is higher than thebus

voltage, the inverter may run at around 0Hz during start.220V voltage level corresponding to bus DC310V;

380V voltage level corresponding to bus DC540V;480V voltage level corresponding to bus DC620V.
E0.02 MPPT Voltage search interval time

0.0

1000.0s

2.0s

MPPT Interval search time when set E0.00 to 2. It indicates the speed of MPPT tracking ,lower numbers

equate to better speed on MPPT tracking,but the MPPT serching interval is short,may result in more

fluctuations on output frequency of the inverter
E0.03 Wake up delay time

0

10000s

300s

When using the sleep function, set F6.13 = 1 (valid).

During the operation of the inverter, when the running frequency is less than E0.09 sleep frequency,

after the E0.11 sleep delay time, the inverter enters the sleep state and decelerates to stop.

If the frequency inverter dormant, run command valid, after E0.03 awakens the delay time,frequency

inverter to start.

E0.04 Upper limit of MPPT search voltage

0.0

1000.0V

Confirmed

model typ

Search value of upper limit voltage in MPPT search process. 220V voltage level search upper limit is

DC400V;380V voltage level search upper limit is DC650V;480V voltage level search upper limit is

DC730V.

E0.05 Lower limit of MPPT search voltage

0.00

1000.0V

Confirmed

model typ

Search value of lower limit voltage in MPPT search process. 220V voltage level search lower limit is

DC270V;380V voltage level search lower limit is DC480V;480V voltage level search lower limit is

DC560V.
E0.06 PID maximum voltage deviation value 0.0

1000.0V

20.0V

When Photovoltaic mode works, by changing parameters, can limit given bus voltage and

current bus voltage’s PID maximum input voltage deviation value

E0.07 Solar wake voltage

0.0

1000.0V

Confirmed

model typ

When inverter is into hibernation, if the bus voltage gradually higher than the set voltage(E0.07), the

inverter will start automatically.220V voltage level wake voltageis DC300V;380V voltage level wake

voltageis DC530V;480V voltage level wake voltageis DC610V.

E0.08 Solar hibernation voltage

0.0

1000.0V

Confirmed

model typ

When inverter is running, when the bus voltage is lower than the set voltage (E0.08),inverter will go

into hibernation.220V voltage level hibernation voltageis DC200V;380V voltage level hibernation voltageis

DC430V;480V voltage level hibernation voltageis DC480V.
E0.09 Hibernation frequency

0~Max frequency(F0.19)

25.00Hz

Hibernation frequency (E0.09) Used with wake-up delay time (E0.03) and hibernation delay

time (E0.11), check E0.03 for functional description.

E0.10 Load drop detection interval time

0

65535s

6000s

When using the load detection interval, set F8.30 ~ F8.32.

After the inverter falls off, Restart the operation after the time which set by E 0.10.

E0.11 Hibernation delay time

0

10000s

100

Hibernation delay time(E0.11)Used with wake-up delay time (E0.03) and hibernation frequency

(E0.09), check E0.03 for functional description.

E1 group Multi-speed, Simple PLC Group

Code

Parameter name

Setting range

Factory

setting Change

E1.00 0-stage speed setting 0X

-100.0%

100.0%

0.0%

E1.01 1-stage speed setting 1X

-100.0%

100.0%

0.0%

E1.02 2-stage speed setting 2X

-100.0%

100.0%

0.0%

E1.03 3-stage speed setting 3X

-100.0%

100.0%

0.0%

E1.04 4-stage speed setting 4X

-100.0%

100.0%

0.0%

E1.05 5-stage speed setting 5X

-100.0%

100.0%

0.0%

E1.06 6-stage speed setting 6X

-100.0%

100.0%

0.0%

E1.07 7-stage speed setting 7X

-100.0%

100.0%

0.0%

E1.08 8-stage speed setting 8X

-100.0%

100.0%

0.0%

Содержание PI500A-S 004G1

Страница 1: ...PI500A S Series Special Solar Inverter For Water Pump English Manual www powtran com...

Страница 2: ...y period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model Designation Powtran Inverter PI 500A S 2R2 G 3 Rated Output Power 2R2 2 2kW 004 4kW Ser...

Страница 3: ...63 185 90 146 154 65 174 5 72 5 1 6 PI500A S 0R7G2 0 75 PI500A S 1R5G2 1 5 PI500A S 2R2G2 2 2 163 185 90 166 174 65 174 5 72 5 1 8 PI500A S 004G2 4 238 260 120 182 190 90 250 5 2 7 PI500A S 5R5G2 5 5...

Страница 4: ...ey is subject to F6 00 Enter Key Enter the menu screen step by step set the parameter confirmation Quick Multifunction Key This key function is determined by the function code F6 21 Keyboard Encoder F...

Страница 5: ...panel control terminals and serial communication port They can be switched through a variety of ways Frequency source Total 8 frequency sources digital analog voltage multi speed and serial port They...

Страница 6: ...ments of all terminals select accessories correctly such as voltmeter input power supply etc 5 Please check the wiring correctly after completion and power on after confirmation 7 The load is a single...

Страница 7: ...motor nameplate Note If the starting current is too large or the motor does not run check whether the V and W phases are connected then check E8 29 3 and then restore the factory value y0 00 3 U V W...

Страница 8: ...24 HDI DI5 pulse frequency HDI DI5 High speed pulse input frequency display unit 1Hz 1Hz d0 25 Communication set value Frequency torque or other command values set by communication port 0 01 d0 27 Mas...

Страница 9: ...cked at the time the parking process of motor is not controlled by the inverter This way is same as the principle of free stop described in F3 07 9 Fault reset RESET The function makes use of terminal...

Страница 10: ...to the function code F7 26 F7 27 s instructions 26 Frequency 1 reaches output Please refer to the function code F7 28 F7 29 s instructions 27 Frequency 2 reaches output Please refer to the function c...

Страница 11: ...0 F4 10 V F overexcitation gain 0 200 80 F4 11 V F oscillation suppression gain 0 100 0 F4 12 V F Separated voltage source 0 9 0 F4 13 Voltage Digital Setting 0V motor rated voltage 0V F4 14 Voltage r...

Страница 12: ...eleration time 2 0 00Hz F0 19 Maximum frequency 0 00Hz F7 15 Switching frequency point between deceleration time 1 and deceleration time 2 0 00Hz F0 19 Maximum frequency 0 00Hz F7 16 Forward reverse r...

Страница 13: ...momentary power cut 0 00s 100 00s 0 50s F8 29 Judgment voltage of momentary power cut action 50 0 100 0 Standard bus voltage 80 F8 30 Load drop protection selection 0 Invalid 1 Valid 0 F8 31 load drop...

Страница 14: ...valid after E0 03 awakens the delay time frequency inverter to start E0 04 Upper limit of MPPT search voltage 0 0 1000 0V Confirmed model typ Search value of upper limit voltage in MPPT search proces...

Страница 15: ...tion Same as E1 19 0 E1 34 8 stage running time T8 0 0s h 6500 0s h 0 0s h E1 35 8 stage ac deceleration time selection Same as E1 19 0 E1 36 9 stage running time T9 0 0s h 6500 0s h 0 0s h E1 37 9 st...

Страница 16: ...motor 0 b0 01 Rated power 0 1 1000 0kW Confirmed model typ b0 02 Rated voltage 1 2000V Confirmed model typ b0 03 Rated current 0 01A 655 35A Inverter power 55kW 0 1A 6553 5A Inverter rate 55kW Confirm...

Страница 17: ...15 Current of the second fault y1 16 Bus voltage of the second fault y1 17 Input terminal status of the second fault y1 19 Output terminal status of the second fault y1 20 Power on time of the second...

Страница 18: ...s high 1 Cancel the external force or install braking resistor 2 Set the voltage to the normal range 8 Err 08 Control power failure 1 The range of input voltage is not within the specification 2 frequ...

Страница 19: ...an the set value of E2 11 Check PID feedback signal or set E2 11 to an appropriate value 40 Err 40 Quick current limiting fault 1 Whether the load is too large or the motor stall occurs 2 The type sel...

Страница 20: ...ing of PI500 PI500A S keyboard installation opening Opening size of external mounting panel T 1 0 1 5mm 126 5 0 2 Mounting panel Opening panel126 5 82 82 0 2 Dimension drawing of keyboard installation...

Отзывы: