page no. 4 oF 28      

    

PZN Aquamatic Water Heater 

 Doc Ref M107 issue 1.3 Sep 2018.  

To maintain efficient, reliable and safe operation of the 

heater it must serviced annually by a qualified person.

This manual is an integral part of the machine, therefore 

it should always be kept safe and it should always be 

provided together with the machine, if it is transferred to 

another owner or user. In case of damage or loss of this 

booklet, request another copy from your local Technical 

Assistance Service or Manufacturer.

Free access must be maintained to and around the heater 

for servicing purposes and the air supply to the heater 

must not be restricted in any way. Combustible materials 

must not be stored adjacent to the heater.

Ensure that any air inlet or outlet louvres of the unit are 

not blocked or restricted in anyway as this may lead to the 

unit malfunctioning.

All Powrmatic units use electricity to power them, they 

may also contain moving parts. It would be hazardous 

to tamper with or attempt to service unless you are a 

competent person in the field of Electrical work.

If you have any safety questions reference the servicing 

and installation of any of our heaters please do not 

hesitate to contact our head office for expert advice. Your 

safety is paramount to us.

 

Excess temperature is damaging to health and represents 

a waste of energy. Do not leave the rooms closed for a 

long time. Periodically open a window to air the room/

building.

If you do not intend to use the unit for a long period of 

time you MUST at least do the following:

•  turn the main switch of the unit and the general 

switch of the plant to "OFF"

•  close the water check valves;

•  if there is a risk of sub-zero temperatures, drain the 

water from the unit.

If the unit has remained idle for a long period it is advisable 

to have it restarted by an authorised Technical Assistance 

Service or, in any case, by professionally qualified 

personnel.

In case of water leaks, turn the main switch "off" and 

close the water taps. Immediately call the Technical 

Assistance Service or professionally qualified personnel 

and do not intervene personally on the unit.

The manufacturer is responsible for the product 

compliance with Laws, Directives or Construction Rules in 

If the heater has not been left operational 

proceed as follows. 

The following preliminary checks should be made before 

operating the unit

a)  Ensure that the ELECTRICAL supply to the unit is 

switched OFF.

b)  The unit is positioned correctly.

c)   Water and electrical connections have been made 

correctly.

d)   Water pressure (unit cold) is as required.

e)   Any air has been bled from the system.

g)  Check that any delivery outlet grilles are open.

h)  Check that the external thermostat is set. (if fitted)

j)   Check that the clock control is set to ON. (if fitted)

k)  Check that any controls are switched on. (if fitted)

l)   Ensure boiler is operational and check valves are open.

•  Switch on the electrical supply at the isolator.

•  Position the main switch to ON.
•  Set fan speed as desired (where speed selector 

switch is installed).

•  Set room thermostat to desired temperature (higher 

than current room temperature).

•  At this point both the water circulator and the 

heater fan start simultaneously. To prevent an initial 

outflow of unpleasant cold air it is possible to delay 

fan start-up with the aid of a minimum thermostat 

(not supplied as accessory). This thermostat also 

delays fan shutdown so as to disperse all the heat 

accumulated in the exchanger into the room/area to 

be heated.

•  Once the temperature set on the room thermostat 

has been reached the heater will shut down. When 

the temperature drops back down below this setting 

the fan heater restarts automatically.

  1) For Short Periods: 

Turn any controls/switches to OFF. 

Turn the thermostat to the OFF

 

(if fitted).

  2) For Long Periods: 

•  Deactivate the fan heater by acting on the room 

thermostat;

•  Turn the main switch to OFF.

•  Close the water check valves.

Содержание PZN 12

Страница 1: ...w w w p o w r m a t i c c o u k d e t 4 3 4 e e PZN User Installation Servicing Manual Issue 1 3 September 2018 Doc Ref M107 Issue 1 3 Sep 2018...

Страница 2: ...your behalf Conditions of Guarantee 1 The heater must have been installed by a competent qualified installer and in accordance with the manufacturer s instructions building regulations and local regul...

Страница 3: ...1 Introduction 4 Duties 6 Dimensions 7 1 2 Technical data 8 1 3 General Requirements 16 Installation 2 1 Fitting the unit 19 2 2 Electrical Cable Installation 21 2 3 Wiring Diagrams 22 2 4 Commission...

Страница 4: ...sionally qualified personnel In case of water leaks turn the main switch off and close the water taps Immediately call the Technical Assistance Service or professionally qualified personnel and do not...

Страница 5: ...s safety Do not touch the heater if you are barefoot or if parts of your body are wet Before carrying out any cleaning and or maintenance work on the unit always disconnect the unit from the mains pow...

Страница 6: ...cal h 36720 33630 45060 47760 54180 58220 75510 76370 98810 Rows no 3 2 3 2 3 2 3 2 3 Axial Fan Qty no 1 2 dia mm 400 420 420 550 550 450 450 550 550 rotations rpm 1400 900 700 900 700 Airflow Rate m...

Страница 7: ...40 690 690 690 C mm 90 116 122 172 162 172 D mm 489 539 589 639 689 739 789 1139 Weight kg 14 15 16 18 19 21 23 24 25 28 29 32 40 43 58 63 70 76 Model 12 13 22 23 32 33 42 43 52 53 62 63 72 73 82 83 9...

Страница 8: ...Outlet Temperature C 48 50 53 Water Side Heat Loss kPa 16 14 11 Water Flow Rate l h 598 546 494 PZN 12 13 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN13 Airflow Rate...

Страница 9: ...ir Outlet Temperature C 40 43 46 Water Side Heat Loss kPa 15 12 10 Water Flow Rate l h 953 869 786 PZN 22 23 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN23 Airflow Rat...

Страница 10: ...Air Outlet Temperature C 46 49 52 Water Side Heat Loss kPa 20 17 14 Water Flow Rate l h 1031 941 85215 PZN 32 33 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN33 Airflow...

Страница 11: ...3 Air Outlet Temperature C 50 52 55 Water Side Heat Loss kPa 13 11 10 Water Flow Rate l h 1161 1059 958 PZN 42 43 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN43 Airflo...

Страница 12: ...43 Air Outlet Temperature C 51 53 55 Water Side Heat Loss kPa 11 10 8 Water Flow Rate l h 1371 1251 1132 PZN 52 53 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN53 Airfl...

Страница 13: ...7 Air Outlet Temperature C 49 52 54 Water Side Heat Loss kPa 7 6 5 Water Flow Rate l h 1668 1521 1375 PZN 62 63 Single Phase 230V 50Hz Water Temp 85 70 C Fan heater at MAXIMUM fan speed PZN63 Airflow...

Страница 14: ...44650 Air Flow Rate m h 6200 Sound Pressure Level dB A 52 Air Outlet Temperature C 45 48 50 Water Side Heat Loss kPa 12 10 8 Water Flow Rate l h 3707 3380 3056 Fan heater at MINUMUM fan speed Airflow...

Страница 15: ...r Flow Rate m h 12550 Sound Pressure Level dB A 53 Air Outlet Temperature C 36 39 43 Water Side Heat Loss kPa 21 18 15 Water Flow Rate l h 5229 4773 4321 Fan heater at MINUMUM fan speed Airflow Rate C...

Страница 16: ...letromagnetic Compatibility Directive 2004 108 EC Low Voltage Directive 2006 95 EC Machinery Directive 2006 42 EC 1 3 3 Handling Handling must be done by properly equipped personnel All units are pack...

Страница 17: ...mental pollution noise emission etc It is therefore advisable before installing the unit to request and obtain the necessary permissions Note For proper installation always observe the following minim...

Страница 18: ...city supply must facilitate the complete electrical isolation of the unit s via a suitable fused isolator see section 2 4 5 for ratings be in a readily accessible position adjacent to the unit s serve...

Страница 19: ...according to the book that is in compliance with the National and Local Standards in force and the instructions provided in this instruction booklet The heaters have been manufactured for room heating...

Страница 20: ...n running a few hours and periodically check pressure check that there are no leaks WARNING If there is a risk of sub zero temperatures mix some anti freeze into the water in manufacturer recommended...

Страница 21: ...conductor if the cable or cord slips out of the cord anchorage All external controls must be of an approved type All units are fully pre wired and only require final connections for the incoming main...

Страница 22: ...50Hz 86 0 38 1 1 5 32 33 230V 50Hz 120 0 55 1 1 5 42 43 230V 50Hz 130 0 60 1 1 5 52 53 230V 50Hz 200 0 90 2 1 5 62 63 230V 50Hz 220 0 95 2 1 5 72 73 400V 3N 50Hz 305 0 70 2 1 5 82 83 400V 3N 50Hz 240...

Страница 23: ...uamatic Water Heater Doc Ref M107 issue 1 3 Sep 2018 2 3 Wiring Diagrams 2 3 3 External Wiring Details PZN 82 93 with two fans without connecting box 2 3 4 External Wiring Details PZN 82 93 with two f...

Страница 24: ...ting the heating function Deactivate the fan heater by acting on the room thermostat Turn the main switch to OFF Close the water check valves WARNING If there is a risk of sub zero temperatures and th...

Страница 25: ...ain all the water WARNING Always switch off and disconnect electricity supply and close the water check valve before carrying out any servicing work or replacement of failed components NOTE If a suspe...

Страница 26: ...nufacturer recommended quantities 2 5 5 Exploded Views 2 5 5 1 PZN 12 73 9 STRUCTURE Structure of Heater Types 1 14 1 Water air exchanger 6 Fixing part 2 Side panel left 7 Fixing part 3 Side panel rig...

Страница 27: ...Fan faulty Check fan motor Condenser faulty Check condenser Overload cut out tripped Check absorption POOR HEATING EFFICIENCY Heat exchanger dirty Clean exchanger Airflow obstructed Remove obstructio...

Страница 28: ...el 353 0 1452 1533 fax 353 0 1452 1764 e mail info powrmatic ie web www powrmatic ie Getting In Touch Powrmatic pursues a policy of continues improvement in both design and performance of its products...

Отзывы: