OUH Range Users, Installation & Servicing Instructions Doc Ref M105 issue 5.8 Apr 2020.
F - Free Blowing Unit
CCF - Centrifugal Unit
Model
Running
Current (A)
Fuse/MCB Rating (A)
Running
Current (A)
Fuse/MCB Rating (A)
(motor rated Protection Device)
OUH20
0.94
3 / 6
4.30
6 / 6
OUH30
0.46
3 / 6
4.33
6 / 6
OUH45
0.48
3 / 6
5.54
10 / 10
OUH60-35s
1.70
3 / 6
8.00
10 / 10
OUH60-28s
1.70
3 / 6
9.76
13 / 13
230V Heat Low Demand
230V Main Fan Only
230V Heat High Circuit
230V Lockout Indication
230V LNE to Controller
terminal 1
terminal 3
terminal 4 & 5
terminal 6
terminal 11, 12 & 13
L
N
E
Out
put 2
30V
In
put 2
30V
Fa
n O
nl
y Si
gn
al 2
30V
He
at O
n Si
gn
al 2
30V
Li
ve O
ut
put
N
eu
tra
l
Ear
th
t1
t3 t4 t5 t6
t10 t11
t
230V Supply
for Controller
High
Fire
Circuit
Lo
ck
out Si
gn
al 2
30V
The wiring terminals are located under the lid of the
electrical box on top of the unit.
Mains input 230V 50Hz 1Ph supply connections are via
a separate LNE terminal block. For input power refer to
table below. Control circuitry / external control mains
connections are via a numbered terminal strip. These
being: