External Bypass Switch Installation
43
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
:
Rev A
www.powerware.com
QFE: 50 Hz 220, 230, or 240 Vac Input and Output OR
FE: 60 Hz 220 Vac Input and Output
For FE 60 Hz 220 Vac, use only a BBM switch.
Figure 15. FE or QFE 4.3–18 kVA UPS with External Bypass Switch
Table 20. Input Current - Size Overcurrent Protection According To Local Code
Voltage
Charger
4.3 kVA
5.3 kVA
7 kVA
10 kVA
12.5 kVA
18 kVA
60 Hz
220 V
Standard
17A
21A
27A
41A
53A
81A
220 Vac
10A
18A
23A
28A
49A
60A
85A
20A
20A
25A
30A
52A
65A
89A
50 Hz
220 V
Standard
19A
21A
27A
43A
55A
81A
220 Vac
10A
22A
23A
28A
46A
58A
84A
20A
23A
25A
29A
51A
63A
89A
50 Hz
230 V
Standard
18A
20A
26A
41A
53A
78A
230 Vac
10A
20A
22A
27A
44A
56A
81A
20A
21A
24A
28A
49A
60A
85A
50 Hz
240 V
Standard
17A
19A
24A
39A
51A
75A
240 Vac
10A
19A
21A
26A
43A
54A
78A
20A
20A
23A
27A
47A
58A
82A
Содержание Ferrups FE
Страница 1: ...Powerware FERRUPS FE QFE UPS Installation Guide 500 VA 18 kVA 50 and 60 Hz...
Страница 2: ......
Страница 3: ...Powerware FERRUPS FE QFE UPS Installation Guide 500 VA 18 kVA 50 and 60 Hz www powerware com...
Страница 28: ...Setup 22 Powerware FERRUPS FE QFE UPS 500 VA 18 kVA Installation Guide Rev A www powerware com...
Страница 76: ...Phase Check 70 Powerware FERRUPS FE QFE UPS 500 VA 18 kVA Installation Guide Rev A www powerware com...