23
Table 7. Battery
Configuration
1000VA; (2) 24V, 9 Ah internal batteries
1500VA; (4) 48V, 7.2 Ah internal batteries
2000VA; (4) 48V, 12 Ah internal batteries
2200VA; (4) 48V, 12 Ah internal batteries
EBM Configuration
EBM-24; (8) 24V, 9 Ah batteries
EBM-48; (8) 48V, 9 Ah batteries
Type
Sealed, maintenance free, valve regulated, lead-acid
Charging
Internal battery; less than 3 hours to 90% usable capacity at nominal after
full load discharge
External battery; recharging at 80% load or less is recommended, no more
than 16x discharge time to 90% usable capacity at nominal line voltage after
full load discharge; an external battery charger is recommended for faster
recharge times when using more than 2 EBMs
Monitoring
Advanced monitoring for earlier failure detection and warning, auto detection
of additional EBMs
Table 8. Battery Run Times (in Minutes at Full/Half Load)
Model
Internal UPS Batteries
1 EBM
2 EBM
3 EBM
4 EBM
1000VA; 5/14
25/60
55/170
83/199
109/228
1500VA; 6/17
33/79
63/146
92/174
120/201
2000VA;
5/16
29/67
62/190
91/222
119/251
2200VA;
5/14
26/60
55/170
81/198
106/224
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge
Powerware reserves the right to change specifications without prior notice.