6. Specifications
MODEL
VFI 6000 CT LCD
VFI 10000 CT LCD
CAPACITY*
6000 VA / 5400 W
10000 VA / 9000 W
INPUT
Voltage Range
Low Line Loss
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Comeback
Low Line Loss V 10V
High Line Loss
300 VAC ± 3 %
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Power Factor
≧
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 30min; 110%~130%: 5min; >130% : 10sec
Battery mode
100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec
Current Crest Ratio
3:1 max
Harmonic Distortion
≦
3 % THD (Linear Load)
≦
5 % THD (Non-linear Load)
Transfer Time
Line
Battery
0 ms
Inverter
Bypass
0 ms
EFFICIENCY
AC mode
> 92%
> 93%
Battery Mode
> 90%
> 91%
BATTERY
Standard
Model
Battery Type
12 V / 9 Ah
Numbers
16
20
16
20
Recharge Time
9 hours recover to 90% capacity
Charging Current
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
Charging Voltage
218.4V ± 1%
273V ± 1%
218.4V ± 1%
273V ± 1%
Long-run
Model
Battery Type
Depending on applications
Numbers
16-20
Charging Current
Default: 4 A ± 10%
Max.: 1A, 2A, 4A, 6A (Adjustable, 6A is only available for 16pcs batteries)
Charging Voltage
218.4V ± 1% (based on 16pcs batteries)
PHYSICAL
Standard
Model
Dimension,DXWXH(mm) 369 x 190 x 688
442x 190 x 688
Net Weight (kgs)
61
74
66
76
Long-run
Model
Dimension, DXWXH(mm)
369 x 190 x 318
442x 190 x 318
Net Weight (kgs)
12
16
ENVIRONMENT
Operation Temperature
0 ~ 50°C
(battery life cycle will be shorten when
temperature is above 25°C)
0 ~ 40°C
(battery life cycle will be shorten when
temperature is above 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB @ 1 Meter
Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and
MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
Содержание VFI 10000 CT LCD
Страница 1: ...PowerWalker VFI 6000 CT LCD VFI 10000 CT LCD Manual Uninterruptible Power Supply System EN DE PL ...
Страница 27: ...PowerWalker VFI 6000 CT LCD VFI 10000 CT LCD Bedienungsanleitung Unterbrechungsfreie Stromversorgung DE ...
Страница 31: ...3 ...
Страница 55: ...PowerWalker VFI 6000 CT LCD VFI 10000 CT LCD Instrukcja obsługi Awaryjny system zasilania PL PL ...