-30-
SHOR
Inverter short
Output short
circuit
Remove all the loads.
Turn off the UPS.
Check whether the
output of UPS and
loads is short circuit.
Make sure the short
circuit is removed, and
the UPS has no
internal faults before
turning on again.
OVTP
Over
temperature fault
Over temperature
Check the ventilation
of the UPS, check the
ambient temperature
and ventilation.
OVLD
Overload
Overload
Check the loads and
remove some
non-critical loads.
Check whether some
loads are failed.
SITE
Site fail
Phase and neutral
conductor at input
of UPS system
are reversed
Rotate mains power
socket by 180° or
connect UPS system.
EPO
EPO active
EPO function is
enabled
Plug into the EPO
switch.
Please have the following information at hand before calling the After-Sales
Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. LCD display status, Buzzer alarm status
4. Utility power condition, load type and capacity, environment temperature,
ventilation condition
5. The information (battery capacity, quantity) of external battery pack
6. Other information for complete description of the problem
Содержание VFI 1000 TG
Страница 1: ...USER MANUAL PowerWalker VFI 1000 2000 3000 TG VFI 1000 2000 3000 TGS ...
Страница 11: ... 8 UPS Block Diagram ...
Страница 39: ... 36 Appendix Rear panel 1000 TG S Back View of Schuko 2000 TG S Back View of Schuko ...
Страница 40: ... 37 3000 TG S Back View of Schuko 1000 TG S Back View of IEC ...
Страница 41: ... 38 2000 TG S Back View of IEC 3000 TG S Back View of IEC 11 04 2016 614 02071 00 ...